background image

3 | COMMISSIONING AND MAINTENANCE

20

3

COMMISSIONING AND MAINTENANCE

3.1

Preparation for first commissioning

Prior to commissioning, it is necessary to check that:

- all the safety conditions have been met
- installation distances and gaps have been respected
- the indoor units have been connected to the respective

refrig-erant and electric circuit

- the electrical connections have been properly completed
- power supply values are correct.
- the earthing has been carried out correctly
- all the connections have been properly tightened
- the shut-off valves are open

The device must always be powered electrically in order to allow for
the compressor's oil to be properly pre-heated.

If the device is installed in very cold areas, the device should be
under voltage for at least 12 hours before starting it up for the first
time.

- position the system's main switch in the "ON" position.
- carry out the verification procedure of the electrical connections

3.2

Putting into service

After having completed all the operations required to prepare for first
commissioning, do the following to activate the device:

- follow the instructions given in the manual of the indoor unit that

you are installing

Keep the leak finder on and close to the unit so that it signals any
refrigerant leak.

Use an electronic leak finder properly calibrated for the system
refrigerant.

It is forbidden to use leak finders with halogen lamps.

Checks during and after the first commissioning

After starting the device, check that:

- the current consumed by the compressor is less than the

maximum permitted

- the device is operating under the recommended operating

conditions

- the unit is able to stop and start up again

Should any of the above-listed controls have problems: turn the
device off and call the Technical Service immediately.

Do not touch the device pipes to prevent potential burns.

Take anti-static precautions in case of weather conditions where
humidity is less than 40%.

Avoid using mobile phones.

Additional refrigerant charge

The units are supplied with a sufficient amount of refrigerant gas for a
pre-set length of the connection pipes.
An additional refrigerant charge is needed if such length is exceeded.
The pre-set values are detailed in the following table:

Model

18000-2

Connection pipes

Maximum length
with standard
charge

m

20

Additional charge

g/m

20

The device must be earthed before performing the additional charge.

To perform the additional charge:

A

High pressure

B

Low pressure

1

Pressure gauge unit

2

Electronic scale

3

3-way valve service connection

- connect the refrigerant cylinder to the pressure gauge unit
- connect the charging tube to the service connection on the

3-way shut-off valve

- remove the air from the charging tube
- charge the refrigerant with an electronic scale
- disconnect the charging tube from the service valve
- refit the three-way valve closing plug

Carefully check for absence of leakages from the closing point of the
plug.

Do not force beyond the stop point to prevent damaging the shaft
and causing leakage as a consequence.

Use equipment suitable for the system refrigerant.

Use only the system refrigerant.

Any gas leaks indoors can generate toxic gases if they come into
contact with naked flames or high temperature bodies, in case of
leaks, please air the rooms thoroughly.

Take anti-static precautions in case of weather conditions where
humidity is less than 40%.

Avoid using mobile phones.

Summary of Contents for 20171586

Page 1: ...Installer manual BREVA EX EN...

Page 2: ...he device s correct and easy installation Thank you again and keep up the good work BERETTA S p A COMPLIANCE BREVA EX heat pumps are compliant with the following European Directives Low Voltage Direct...

Page 3: ...to service 3 3 Ordinary maintenance 3 4 Segnalazione di funzionamento e allarmi 4 DISPOSAL The following symbols are used on the product The R32 refrigerant gas is slightly inflammable and odourless A...

Page 4: ...rigerant gas operate carefully so as to avoid damaging the gas circuit and the fin bank Do not place any inflammable object spray cans within a 1 metre radius from the air expulsion According to EU Re...

Page 5: ...ectronic board that is triggered when the heat exchanger is clogged by frost formations suction temperature sensor which transmits the detected value to the electronic board that is triggered in order...

Page 6: ...Wh annum 269 Heating performance 3 Capacity at rated air flow kW 5 20 Capacity at minimum air flow kW 1 60 Capacity at maximum air flow kW 6 10 Absorbed power at rated air flow kW 1 40 Absorbed power...

Page 7: ...x current input A 12 50 Minimum current consumption A 2 50 Electrical characteristics Power supply V Ph Hz 220 240 1 50 Compressor Compressor Tipo Rotativo Doppio Oil Tipo RM LP56EG Oil charge l 0 48...

Page 8: ...7 3 5 A 6 5 A Heating Combinations Single nominal capacity Total nominal capacity Total power input Total current input COP Energy class SCOP Energy class Indoor units Indoor units A B Unit A Unit B M...

Page 9: ...nd delivers it to the room air thereby heating it During the summertime the cycle is reversed and the thermal energy is extracted from the room air which is cooled and is delivered to the outdoor air...

Page 10: ...ocument envelope Instruction s book for the installer and for the Technical Service in Italian Instruction s book for the installer and for the Technical Service in English Warranty Spare parts labels...

Page 11: ...cking material must not be disposed of in the surrounding environment and must be kept out of children reach as it can be dangerous It must be disposed of according to the regulations in force 2 6 Pla...

Page 12: ...ent the air flow from being blocked or install a roofing to protect it Adequate anti freeze systems should be used for installations in extremely cold areas where there is a possibility of freezing Wh...

Page 13: ...ing table Model 18000 2 Connection pipes h1 m 7 50 h2 m 7 50 h max m 15 H m 15 H m 15 L1 L2 m 20 L1 L2 m 30 Maximum length with standard charge m 20 Additional charge g m 20 The R32 refrigerant gas is...

Page 14: ...8 60 Pipe A mm inches mm 6 35 1 4 17 9 52 3 8 22 12 7 1 2 26 15 88 5 8 29 bring line ends with flare connection close to their coupling on the unit manually rotate the flare nuts by 3 4 turns tighten...

Page 15: ...lug 5 Hex wrench If required remove the valve covering plug operate on the valve shaft with an hex wrench open or close according to what is needed immediately stop as soon as the valve shaft has reac...

Page 16: ...let the vacuum pump work for at least 15 minutes reach a pressure that is close to 0 1 Mpa close the low pressure valve of the pressure gauge unit switch off the vacuum pump wait 5 minutes check that...

Page 17: ...se the same vacuum pump with different refrigerants The vacuum pump requires regular maintenance and the oil s clarity must also be checked After having created the vacuum and established the electric...

Page 18: ...must be powered with a separate electric circuit 1 Electric connection input position the system s main switch in the OFF position Wait 10 minutes before touching the device electric components Check...

Page 19: ...esponds to the nominal value 10 with a maximum phase imbalance of 3 all of the power network disconnect devices must be equipped with contact openings 3 mm in order to allow for complete disconnection...

Page 20: ...nded operating conditions the unit is able to stop and start up again Should any of the above listed controls have problems turn the device off and call the Technical Service immediately Do not touch...

Page 21: ...ck with a tester that the voltage between the power supply connectors of the main electronic board is lower than 10 Vdc Yearly operations The annual maintenance plan includes the following checks powe...

Page 22: ...ion booklet for the installer Tabella allarmi Faults are signalled by means of LED 1 blinking Led 1 Description 1 External unit microprocessor fault 2 Power module fault IPM 3 Main electronic board pr...

Page 23: ...shall be disposed of separately so as to recover and recycle them Refrigerant and oil must be recovered and not dispersed into the environment At the end of its service life the device shall be dispo...

Page 24: ...1 277111 Fax 39 0341 277263 info berettaboilers com www berettaclima it As the manufacturer is constantly improving its products the aesthetic or dimensional features the technical data the equipment...

Reviews: