6
Bentone
Control system
10 years
250,000 starts
Valve control system
10 years
250,000 starts
Pressure switch
10 years
250,000 starts
Ignition system with flame guard
10 years
250,000 starts
UV flame sensor
10000 hrs
N/A
Gas pressure regulators
15 years
N/A
Gas valve without seal testing
10 years
250,000 starts
Gas valve with seal testing
Replacement upon fault detection
N/A
Gas pressure switch
10 years
250,000 starts
Safety blow-off system
10 years
N/A
Damper motor
N/A
500,000 starts
Contactor
10 years
500,000 starts
Burner
1 year
3000 hrs
Inspection of electrical installation
1 year
3000 hrs
Leakage check
1 year
3000 hrs
Filter
1 year replacement at Δp>10 mbar
3000 hrs replacement at Δp>10
mbar
Electrodes
Replacement/Cleaning 1 year
Replacement/Cleaning 3000 hrs
Brake disc
Replacement/Cleaning 1 year
Replacement/Cleaning 3000 hrs
Motor
1 year
3000 hrs
Fan wheel
1 Year
Replacement when cleaning
needed/ imbalance
3000 h
Replacement when cleaning
needed/ imbalance
The burner and its components must be recycled according to applicable regulations.
Burner servicing schedule
Servicing must be carried out once a year or after 3000 hours of operation
Component replacement intervals
Delivery check
• Make sure everything is delivered and the goods have not been
damaged during transit.
• If something is wrong with a delivery, report it to the supplier.
• Transport damage must be reported to the shipping company.
Summary of Contents for STG 120/2
Page 17: ...17 Bentone 4 9 Gas nozzle Inner assembly Natural LPG Natural gas LPG 2 5 8...
Page 35: ...35 Bentone 172 615 76 2020 10 16 2 9 1 Wiring diagram Gas burner control LME21...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...