2.3
Gas categori es, approved gases
Only dry gas is permitted for use.
2.2
Capacity range
2.4
Technical specification
BG 300
G20
50 - 200
5.3
21.2
360
G25
50 - 170
6.2
20.9
360
G30 65 - 200
2.0
6.2
360
G31
50 - 200
2.0
8.2
360
160302-179-2
Capacity
kW
Gas quantity
at min. power
Nm
3
/h
Gas quantity
at max. power
Nm
3
/h
Max.
connection
pressure mbar
Min
connection
pressure mbar
See data plate.
Gas quantity and capacity vary according to grade of gas and connection pressure.
Measurements according to EN 15036-1:2006
Alt.1 The noise level of the burner can be reduced by equipping the burner
with silencer. Installation must be done so it does not prevent air supply
to the burner.
Alt.2 The burner’s noise level can be reduced by connecting the burner’s air
intake to the air duct that opens into an appropriate location. Installation
must be done so it does not prevent air supply to the burner.
BG 300
Main supply
1)
230V, 1~, 2.1/3.0A, 50Hz, IP20
Max fuse rating
6.3A
NO
X
-class
2 G20, G25 / 3 G30, G31
Noise level
82dBA
1)
Max operating current, see data plate.
Category
Country of destination
Supply pressure
II
2R3R
AT, BE, BG, CH, CY, CZ, DE, DK, EE, ES, FI, FR, GB, GR,
HR, HU, IE, IS, IT, LT, LU, LV, MK, MT, NL, NO, PL, PT, RO,
RS, SE, SI, SK, TR
20 mbar
II
2H3B/P
AT, CH, CY, DK, FI, LT, RO, SE, SK
20 mbar
II
2H3P
GB, IE
20 mbar
II
2L3B/P
NL, RO
20 mbar
II
2E3B/P
PL
20 mbar
I
2E(R)B
BE
20 mbar
I
3P
BE
20 mbar
160302-180-3