3. General instructions
3.1 General instructions
Oil burners must be installed in accordance with local regulations. The
installer must therefore be knowledgeable of the regulations pertaining to oil
and combustion.
Only oil suitable for the burner must be used and then in combination with a
suitable oil filter installed before the burner’s oil pump.
If the burner is replacing an existing burner, ensure that the oil filter is
replaced or cleaned. Installation may only be performed by qualified
personnel.
Care should be taken by the installer to ensure that electrical cables and oil
lines are not pinched or otherwise damaged during installation or servicing
3.1.1 Installation and Maintenance Manual
The maintenance instructions supplied with the burner must be kept at an
easily accessible location in the boiler room.
3.1.2 Instructions
The user must be comprehensively instructed in the operation of the oil
burner and entire system. It is the responsibility of the supplier to instruct the
user.
3.1.3 Inspection and maintenance
Refer to servicing schedule
3.1.4 Start-up
In order to obtain the correct setting, a flue gas analysis and temperature
measurement must be carried out. Otherwise, there is a risk of soot build up,
poor efficiency or condensation in the chimney. The system must be fine-
tuned at start-up. The temperature in the chimney at a depth of 0.5 m must
be at least 60 °C to prevent condensation.