Two-pipe system

Height

Pipe diameter

H

ø8 mm

m

m

0,0

27

-0,5

23

-1,0

20

-2,0

13

-3,0

6

-4,0

0

Height

Pipe diameter

H

ø6 mm

m

m

Height

Pipe diameter

H

ø8 mm

m

m

4,0

55

3,0

48

2,0

41

1,0

34

0,5

31

0,0

27

Height

Pipe diameter

H

ø6 mm

m

m

4,0

72

3,0

63

2,0

54

1,0

45

0,5

41

0,0

37

INSTRUCTIONS PUMP TYPE SUNTEC AS67C

1-pipe system

1-pipe system

SUCTION LINE TABLES

The suction line tables consist of
theoretically calculated values where
the pipe dimensions and oil velocity
have been matched so that turbulences
will not occur. Such turbulences will
result in increased pressure losses and
in acoustic noise in the pipe system. In
addition to drawn copper piping a pipe
system usually comprises 4 elbows, a
non-return valve, a cut-off valve and an
external oil filter.
The sum of these individual resistances
is so insignificant that they can be
disregarded. The tables do not include
any lengths exceeding 100 m as
experience shows that longer lengths
are not needed.
The tables apply to a standard fuel oil of
normal commercial quality according
to current standards. On commis-
sioning with an empty tube system the
oil pump should not be run without oil
for more than 5 min. (a condition is that
the pump is being lubricated during
operation).
The tables state the total suction line
length in metres at a nozzle capacity of
20 kg/h. Max. permissible pressure at
the suction and pressure side is 2,0
bar. For two-pipe system Q

max

 75 l/h

pump capacity at 15 bar.

COMPONENTS

1. Pressure adjustment
2. Return plug
3. Nozzle outlet G 1/8"
4. Pressure gauge  port G 1/8"
5. Vacuum gauge port G 1/8"
6. Return line G 1/4"

and internal by-pass plug

7. Suction line G 1/4"
8. Pressure gauge  port G 1/8"

With an underlying tank a 1-pipe-
system is not recommended

TECHNICAL DATA

Viscosity range:

2-12 mm

2

/s

Pressure range:

9-15 bar

Oil temperature:

max 60°C

Two-pipe system

171 505 11  96-01

H

H

Summary of Contents for B40A

Page 1: ...1 171 615 82 05 01 Installation and maintenance instruction B40A...

Page 2: ...178 004 53...

Page 3: ...itionelectrodes 4 Nozzleassembly 5 Ignition cable 6 Ignition transformer 7 Photo cell 8 Controlbox 9 Resetbutton 10 Cover inspection glass 11 Fanwheel 12 Motor 13 Nozzleassemblyadjustment 14 Blasttube...

Page 4: ...alue of 11 86 kWh kg for light oil has been used Note that the spray angle and the spray pattern change with the pump pressure 195 400 B 420 200 230 DIMENSIONS RECOMMENDED NOZZLE Because of different...

Page 5: ...carried out in accordance with local regulations The installer of the burner mustthereforebeawareofallregulations relating to oil and combustion Onlyoilsuitablefortheburnershouldbe used and then in c...

Page 6: ...at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipe by loosening screw A 1 Loosen or swing out the burner from the boiler 2 Loosen 2 fixing screws and with...

Page 7: ...re starts Post ignition 2 If a post igniton of 15 s is wanted move the ignition transformer from terminal 7 to terminal 6 LOA24 173 LIST OF COMPONENTS A1 Oil burner control R1 Photoresistor A2 Twinthe...

Page 8: ...disregarded The tables do not include any lengths exceeding 100 m as experience shows that longer lengths are not needed Thetablesapplytoastandardfueloilof normal commercial quality according to curr...

Page 9: ...closedandbecause of the full speed of the gear set the pressure necessary to open the valve will be built up very rapidly AS Solenoid valve with cut off Gear set capacity see pump capacity curves C 67...

Page 10: ...79 7 97 94 81 2 00 6 65 79 68 7 06 84 72 7 45 88 76 7 81 93 80 8 18 97 83 8 49 101 86 8 81 104 90 9 12 108 93 2 25 7 49 89 76 7 94 94 81 8 38 99 85 8 78 104 89 9 18 109 94 9 55 113 97 9 91 117 101 10...

Page 11: ...not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue dr...

Page 12: ...ument s following the provisions of Directive if applicable Place and date of issue name and signature of equivalent marking of authorized person DECLARATION OF CONFORMITY BENTONE BENTONE Ulf Bondeson...

Page 13: ...10 1 4 3 0 3465 0 2 to 1 1 CE 0036 0134 98 16 6 35 6 03 09 93 to 0 25 B 10KA 2 0 4 6 3778 0 2 to 0 95 CE 0036 0135 98 23 7 54 5 18 10 96 to 0 1 B 10ZHV 1 2 2 5 3525 0 2 to 1 0 CE 0036 0136 98 14 2 29...

Page 14: ...0 3592 0 2 to 9 25 CE 0036 0148 98 142 2 699 2 10 11 94 to 0 1 B 60 2F 20 0 90 0 3466 0 3 to 11 4 CE 0036 0149 98 237 0 1066 5 03 09 93 to 0 8 B 60 3F 20 0 90 0 3591 0 3 to 11 4 CE 0036 0150 98 237 0...

Reviews: