7.5.2 UV –detector (QRC)
Should not be exposed to temperatures higher than 60 °C. The current
passing through the UV-detector, when it is lighted, should be at least 70 µA.
The current can be measured with a moving coil instrument. A check is
necessary only if a malfunction is suspected.
7.5.3 Flame monitoring UV-detector (QRC)
Technical data
For continuous operation!
Idle voltage at ION-terminals
AC 115-230V
!
Protect the ionisation electrode from electric
shock!
Short-circuit current
Max. AC 100-300 mA
Max. current for flame detection
Max. DC 5.5 µA
Required current to ensure detection
Min. DC 40 µA
Possible detection current
Max. DC 60 µA
Operational indicator lamp flashes green
<45 µA DC
Operational indicator lamp shines green
>45 µA DC