Tachometer Operation
TRANSDUCER INPUT
(NOTE 1)
SYSTEM KEYPHASORS
* 7200/3000 PROXIMITOR
MAGNETIC
PICKUP
TRANSDUCER
THRESHOLD MODE
(NOTE 3)
MANUAL
* AUTOMATIC
TRANSDUCER
CONDITIONING
HYSTERESIS
0.2 VOLTS
* 0.5 VOLTS
1.0 VOLTS
2.0 VOLTS
ALERT MODES
* OVER ALERT
UNDER ALERT
* LATCHING
NON-LATCHING
FIRST OUT ALERT
(NOTE 2)
* ENABLED
DISABLED
ALERT BYPASS
ENABLED
* DISABLED
RECORDER
OUTPUTS
* + 4 TO +20 mA
+1 TO + 5 Vdc
0 TO -10 Vdc
83870-01
5
PROGRAMMABLE OPTIONS
* OPTIONS SHIPPED FROM BENTLY NEVADA
NOTE 1: MAGNETIC PICKUPS ARE NOT ALLOWED FOR ZERO SPEED APPUCATIONS.
NOTE 2: ALL VERSIONS OF THE TACHOMETER DRIVE ONLY THE RACK FIRST OUT ALERT BUS.
THIS MONITOR DOES NOT DRIVE THE RACK FIRST OUT DANGER BUS.
NOTE 3: THE ZERO SPEED TACHOMETER IS SHIPPED IN THE MANUAL THRESHOLD MODE. AUTO THRESHOLD
IS NOT ALLOWED IN THE ZERO SPEED MONITOR. AUTO THRESHOLD WILL NOT WORK BELOW 5 Hz
(300 RPM AT ONE EVENT PER REVOLUTION).