Bently Nevada 19045 Installation Manual Download Page 13

Section 2 -  INSTALLATION 

 

9

ADJUSTMENT 

Adjustment requires measuring the LVDT output with the linkage set at the zero-
expansion point. Perform all adjustments as accurately as possible. The user may 

construct a gaging tool, if desired, to aid in accurately adjusting the LVDT core 
position during calibration. Table 2-1 lists recommended equipment for 
adjustment. If LVDT power (-24 Vdc) is available from the instrument, the DC 
Power Supply is not necessary. 

LVDT linkage adjustment is performed in the following manner. 

a.  Disconnect the linkage at the machine case attaching point. 

b.  Supply the specified transducer power to the LVDT from the BNC instrument 

or, if necessary, from the DC Power Supply.  Check the voltage at the + and - 
PWR terminals at the terminal block. 

c.  Connect the DMM to SIG and COM at the terminal block. 

d.  Manually adjust core position until the DMM displays 0.00 Vdc. 

e.  Move the LVDT core as follows: 

If full scale expansion is toward-LVDT, move core away from the LVDT 
exactly half the meter range of the indicator. 

If full scale is away-from-LVDT, move core toward the LVDT exactly half the 
meter range of the indicator. 

The core is positioned for correct output signal at zero expansion of the 
machine case.  Mark or secure the core at this position. 

f.  Adjust the linkage carefully (with LVDT core at the zero-expansion position 

set in step e) until the machine end of linkage is located at the zero-
expansion position of the attaching point on the machine case.    Secure the 
linkage adjustments. 

g.  Check the meter at the instrument to assure that linkage movement 

produces the proper upscale/downscale meter response. 

h.  Connect the linkage to the machine case. 

 

 

 

 

Summary of Contents for 19045

Page 1: ...Part Number TW8029303 Rev D 08 07 Bently Nevada Asset Condition Monitoring Installation Manual DC LVDT Housing Assembly Model 19045 19046 19047...

Page 2: ...is document is subject to change without notice Contact Information The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local representative Mailin...

Page 3: ...t the end of its use are solely responsible for the proper disposal of the product No person firm corporation association or agency that is in control of product shall dispose of it in a manner that i...

Page 4: ...DC LVDT Housing Assembly Model 19045 19046 19047 Installation Manual iv Contents 1 DESCRIPTION 1 2 INSTALLATION 5 3 MAINTENANCE 11 4 RECOMMENDED SPARE PARTS 12 5 APPENDIX SPECIFICATIONS 13...

Page 5: ...a machine case as operating conditions vary The LVDT is connected mechanically between a reference point on the machine foundation and a point on the machine that exhibits the measured expansion Inpu...

Page 6: ...6 AXX 01 DC LVDT Housing Assembly with Model 2000 HR DC LVDT 02 DC LVDT Housing Assembly with Model 2000 HR DC LVDT 19047 AXX 01 DC LVDT Housing Assembly with Model 2000 HR DC LVDT 9 25 in span max 02...

Page 7: ...t of phase that are coupled to the primary by the movable core Core position determines the output voltage amplitude of each secondary The secondary outputs are applied to a demodulator which produces...

Page 8: ...DC LVDT Housing Assembly Model 19045 19046 19047 Installation Manual 4 Figure 1 2 DC LVDT Output versus Core Position...

Page 9: ...ning repair or replacement in accordance with the guarantee OPERATING DIRECTION Correct function of the LVDT instrument system requires that the transducer be properly oriented to the measured machine...

Page 10: ...general linkage design should conform to the following guidelines 1 Linkage must not bind throughout the travel range 2 Linkage weight must not be borne by the LVDT 3 Adjustment provision is required...

Page 11: ...unting location Refer to Figures A 2 A 3 and A 4 outline of LVDT housing assemblies for dimensions and component locations Housing mounting holes are determined by the user b Attach the connecting lin...

Page 12: ...ve voltage conductors do not become cross wired An OK indication may be obtained but the equipment will not be operational Prolonged cross wired connection can change the output stage characteristics...

Page 13: ...ls at the terminal block c Connect the DMM to SIG and COM at the terminal block d Manually adjust core position until the DMM displays 0 00 Vdc e Move the LVDT core as follows If full scale expansion...

Page 14: ...Installation Equipment RECOMMENDED EQUIPMENT EQUIPMENT SPECIFICATIONS Hewlett Packard HP970A 3 1 2 digit display with Digital Multimeter DMM 0 to 1000 Vdc 0 to 1000 Vac 0 to 1000 mA dc 0 to 1000 mA a...

Page 15: ...he Specifications and related drawings for necessary dimensions c Connect the DMM to the LVDT SIG and COM terminals The voltage should measure 0 Vdc 0 5 volt d Measure the LVDT outputs with the core p...

Page 16: ...ntenance are listed below If the instrument system is located in a remote area or is used on an extremely critical application several spares may be desired To order replacement units specify the comp...

Page 17: ...to 71 C Storage 54 C to 93 C Shock 250 g for 11 ms Vibration 10 g 0 to 2 kHz Construction Body Series 400 magnetic stainless steel Coil Laminated glass epoxy Lead Wire 24 gage stranded copper Teflon i...

Page 18: ...ohm 200 k ohm Physical See Figure A l Body Length A 6 75 171 8 1 206 11 5 292 Body Diameter B 0 812 20 6 Body End to NuU Center C 2 73 69 3 3 41 86 6 4 99 126 7 Core Length D 3 15 80 4 25 108 5 30 135...

Page 19: ...Section 5 APPENDIX SPECIFICATIONS 15 Figure A l DC LVDT Dimension Identification...

Page 20: ...DC LVDT Housing Assembly Model 19045 19046 19047 Installation Manual 16...

Page 21: ...Section 5 APPENDIX SPECIFICATIONS 17...

Page 22: ...DC LVDT Housing Assembly Model 19045 19046 19047 Installation Manual 18...

Reviews: