Bentel MCP200CS Quick Start Manual Download Page 2

GENERAL DESCRIPTION

The MCP200CS Manual Call Point has been specially designed
to be used with Conventional Fire Alarm Systems and is ideal for
internal installations that require manual activation and inhibi-
tion of Fire Alarms and Fire Extinquishment Systems.
The MCP200CS Manual Call Point is activated by pushing the
centre of the Operating Face (black arrows indicate the exact
point), and reset by means of the special key, it provides also local
LED indication of Alarm status (Red LED Fixed).

ACTIVE STATUS

Once happens any fire, user can push the plastic button of the
Manual-Call-Point down (see fig 4) then a warning YELLOW-
BOARD would jump up. When the Yellow-Board shows off, it
means the MCP has been activated. The red LED is also switched
on drawing the alarm current from the conventional zone.

RESET

When the MCP has been settled down, the security manager can
reset the Manual-Call-Point back to its stand-by status by using the
attached KEY (see fig 1); whom can find the key hole on the right-
side of Manual-Call-Point then push the key into and till its end,
then pull it out to complete the RESET action.

KEY'S FUNCTION

The key can also be used to disassembly the main-unit out from its
base. User can find two small square holes at the bottom side of
the Manual-Call-Point, whom can use the key to push the springs
of main-unit out through the holes then can easily to depart the
whole Manual-Call-Point into two parts (see fig 3).

INSTALLATION

1.

 Please use a standard screw driver to fix the base onto its proper

position, then according to the following description to make the
wires connect to the Manual-Call-Point.

2.

 Pull the connection wires out through the hole of the base-unit.

3.

 Connected the wires into the L and C wire-holders (there are

each two holes under both L and C labels for Input or Output). Just
push about 5mm of the wire-lead into the wire-holder then the
wire will be auto locked down.

4.

 Insert the main unit of Manual Call Point into the base unit and

push it down to fix them together.

G

G

G

G

G

  ENGLISH

WIRING DIAGRAM

The Module can be connected to the Conventional Zone by
means of a standard two wire connection (See Fig. 2).
In the alarm condition the Manual Call Point LED is turned on,
two resistors in parallel limit the current that flows into the LED
and the resultant limiting resistor is 270 ohm.
The alarm current determined by this resistor value can meet the
ranges of typical fire conventional panels and allows, on the
Bentel panels, to discriminate alarms from MCP’s or from fire
detectors that have been wired on the same conventional zone.
If the higher alarm resistance (470 ohm) option is required remove
the internal cover 

B

 (fig 5) and cut the resistor 

C

.

The supervision of the conventional zone is achieved by connect-
ing the End Of Line Resistor, 3.9 kohm for the Bentel panels.

ELECTRICAL DETAILS

63(&,),&$7,216

9$/8(

 #)* 

,-.

" + ,

"  

(('

/

  

-!  !"

 

." ) + 

!" #

/%

 

)&%01'2(&'(%13*'

+1%*&4

Recycling information

Bentel recommends that customers dispose of their used equipments (panels, detectors, sirens, and other devices)

in an environmentally sound manner. Potential methods include reuse of parts or whole products and recycling of products, components, and/or materials.

For specific information see: 

http://www.bentelsecurity.com/en/environment.htm

Waste Electrical and Electronic Equipment (WEEE) Directive

In the European Union, this label indicates that this product should NOT be disposed of with household waste.

It should be deposited at an appropriate facility to enable recovery and recycling.

For specific information see: 

http://www.bentelsecurity.com/en/environment.htm

BENTEL SECURITY srl reserves the right to modify the technical specifications of this product without prior notice.

Summary of Contents for MCP200CS

Page 1: ...allarme della zona convenzionale RIPRISTINO Una volta attivato l MCP il responsabile della sicurezza può riportarlo al suo stato di riposo tramite la chiave in dotazione vedere fig 3 inserire la chiave nel foro posizionato sulla parte destra dell MCP spingendola fino in fondo quindi estrarla per completare l azione di ripristino FUNZIONI DELLA CHIAVE La chiave può anche essere usata per smontare l...

Page 2: ...wire holders there are each two holes under both L and C labels for Input or Output Just push about 5mm of the wire lead into the wire holder then the wire will be auto locked down 4 Insert the main unit of Manual Call Point into the base unit and push it down to fix them together G G G G G ENGLISH WIRING DIAGRAM The Module can be connected to the Conventional Zone by means of a standard two wire ...

Page 3: ...guridad puede resetear el pulsador de incendio al estado de reposo usando la llave de reset ver Fig 1 el orificio para la llave de reset se encuentra en el lado derecho del pulsador luego se presiona la llave dentro del mismo hasta que haga tope al desaparecer el fondo amarillo el pulsador se habrá rearmado FUNCIÓN DE LA LLAVE La llave puede ser también empleada para desmontar la unidad principal ...

Page 4: ...Dimensioni Dimensions Dimensiones Fig 4 Elemento di attivazione ripristinabile Fig 4 Elementos de plástico ajustables Fig 4 Elementos de plástico ajustables Fig 5 Taglio resistore Resistor cut Corte resistencia Fig 2 Collegamenti Connections Conexiones ...

Reviews: