Operating manual 

DUSPOL

®

 expert

Before using the voltage tester DUSPOL

®

 expert: 

Please  read  the  operating  manual  carefully  and 

always observe the safety instructions!

List of contents:

1.   Safety instructions 

2.   Functional description of the voltage tester

3.   Functional test of the voltage tester 

4.   How to test AC voltages

4.1   How to test the phase at AC voltage

5.  How to test DC voltages

5.1  How to test the polarity at DC voltage 

6.   How  to  test  the  phase  sequence  of  a  three-

phase mains

7.   How  to  test  an  electrically  conductive 

connection (continuity check) 

8.   Battery replacement

9.   Technical data

10.   General maintenance

11.   Environmental notice

1.  Safety instructions:

-   Hold  the  voltage  tester  only  by  the  insulated 

handles    and    and  do  not  touch  the  contact 

electrodes (probe tips) 

-   Immediately before use: Check the voltage tester 

for correct operation! (see chapter 3). The voltage 

tester must not be used if one or several display 

functions fail or if the voltage tester is not ready to 

operate (IEC 61243-3)! 

-   At  operating  sites  with  a  high  noise  level,  it  has 

to be checked before use if the test signal can be 

perceived.

-   The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to AC 690 V/ DC 

750 V!

-   Do not operate the voltage tester with the battery 

compartment being open! 

-   The voltage tester complies with protection class 

IP 64 and therefore can also be used under wet 

conditions (designed for outdoor use). 

-   For testing, firmly grasp the voltage tester by the 

handles   and  . 

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)! 

-   The  voltage  tester  only  operates  correctly 

within  the  temperature  range  of  -10 °C  up  to 

+55 °C at relative air humidity of 20 % up to 96 %.

-   Do not dismantle the voltage tester!

-   Please  protect  the  housing  of  the  voltage  tester 

against contamination and damages! 

-   Please  store  the  voltage  tester  under  dry 

conditions.

-   To  prevent  injuries  and  discharge  of  the  battery, 

provide  the  contact  electrodes  (probe  tips)  with 

the enclosed cover after using the voltage tester! 

Attention: 

After  maximum  load  (i.e.  after  a  measurement  of  30 

seconds  at AC  690 V/  DC  750 V),  the  voltage  tester 

must not be used for a duration of 240  seconds!

The voltage tester is marked with international electric 

symbols and symbols for indication and operation with 

the following meaning: 

symbol

meaning
Device or equipment for working under 

voltage

Push button

Alternating current (AC)

Direct current (DC)

Direct and alternating current (DC and 

AC)
Push  button  (manually  actuated); 

indicates  that  respective  indications 

only occur when both push buttons are 

actuated

Phase-sequence clockwise

Phase-sequence  indication;  the  phase 

sequence  can  only  be  indicated  at  50 

or 60 Hz and in a earthed mains

This  symbol  shows  the  correct 

alignment  of  the  batteries  to  ensure 

correct polarity 
Signal lamp, optical signal for continuity 

check

Buzzer,  acoustic  signal  for  continuity 

check

Symbol for phase and phase-sequence 

indication (phase-sequence clockwise) 

2.   Functional description 

The  DUSPOL

®

  expert  is  a  two-pole  voltage  tester 

according  to  IEC  61243-3  with  visual  display.  As  a 

supplementary  device,  the  voltage  tester  is  equipped 

with  a  phase  indication,  phase-sequence  indication, 

measuring  point  illumination  and  a  continuity  check 

function.  The  supplementary  functions  –  except  the 

phase  indication  –  are  supplied  via  two  replaceable 

micro  batteries  (LR  03/  AAA).  The  signalling  of  the 

continuity  check  is  done  optically  and  acoustically. 

The voltage tester is designed for DC and AC voltage 

tests within the voltage range of 12 V up to AC 690 V/ 

DC 750 V. It can be used to perform polarity tests in DC 

and phase tests in AC. The voltage tester indicates the 

phase-sequence provided that the neutral is earthed. 

The  voltage  tester  consists  of  the  test  probes  L1   

and L2   and a connecting cable 

. The test probe 

L1   is equipped with a display 

. Both test probes 

are  provided  with  push  buttons 

.  Without  pressing 

both  push  buttons,  the  following  voltage  steps  (AC 

or  DC)  can  be  indicated:  24 V+;  24 V-;  50 V;  120 V; 

230 V; 400 V; AC 690 V/ DC 750 V. By pressing both 

push  buttons,  the  voltage  tester  switches  to  a  lower 

internal  resistance  (suppression  of  inductive  and 

capacitive voltages). Thus, also the indication of 12 V+ 

and 12 V-  is activated. Furthermore, a vibrating motor 

(motor  with  a  flyweight)  is  put  under  voltage.  From 

approximately 200 V this motor is set in rotation. With 

the voltage increasing, the motor’s speed and vibration 

increases as well so that additionally by means of the 

handle  of  test  probe  L2    the  voltage  value  can  be 

estimated  roughly  (e.g.  230/  400  V). The  duration  of 

the test with a lower internal resistance of the device 

(load  test)  depends  on  the  value  of  the  voltage  to 

be  measured.  To  prevent  excessive  warming  of  the 

voltage tester, it is equipped with a thermal protection 

(reverse control). With this reverse control, the speed 

of the vibrating motor decreases as well. 

The  measuring  point  illumination  can  be  activated 

by  pressing  the  push  button 

  of  test  probe  L1  . 

For  the  voltage  measurement  with  ripple  (two-pole 

measurement),  the  illumination  is  activated  with 

reduced  brightness.  The  activation  of  the  continuity 

check can be introduced by bringing together the two 

contact electrodes 

Display field

The  display  system  consists  of  high-contrast  light-

emitting  diodes  (LED) 

  indicating  DC  and  AC 

voltages  in  steps  of  12;  24;  50;  120;  230;  400;  AC 

690 V/ DC 750 V. The indicated voltages are nominal 

voltages. With DC voltage, the LEDs also indicate the 

polarity  for  12 V  and  24 V  (see  chapter  5). The  12 V 

LED  can  only  be  activated  by  pressing  both  push 

buttons. 

LC display

The  LC  display 

  serves  for  the  phase  test  with 

alternating  current  (AC)  and  indicates  the  phase-

sequence of a three-phase mains.

3.  Functional check 

-   The  voltage  tester  must  be  used  only  within 

the  nominal  voltage  range  of  12 V  up  to  

AC 690 V/ DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Check  the  voltage  tester  for  correct  function 

immediately before use! 

-   Test  all  functions  by  means  of  known  voltage 

sources. 

 

•   For DC voltage tests use e.g. a car battery. 

 

•   For AC voltage tests use e.g. a 230 V socket.

 

•   Connect both contact electrodes 

 to test the 

continuity check for correct function. 

 

•   Check  the  battery  status  for  the  phase-

sequence  indication  by  activating  the 

measuring  point  illumination.  Replace  the 

batteries, if necessary. 

Do not use the voltage tester unless all functions are 

operating correctly!

Check the function of the LC display 

 

by single-pole 

connection of the contact electrode 

 

of the test probe 

L1   to an external conductor (phase).

4.  How to test AC voltages 

-   The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to AC 690 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly  grasp  the  insulated  handles    and    of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   For  AC  voltages  from  24 V  onwards  and  when 

pressing both push buttons (load test) from 12 V 

onwards, the LEDs “plus” and “minus” 

 and 

 

light up. Furthermore, all LEDs light until the step 

value of the applied voltage is reached. 

-   When  pressing  both  push  buttons 

  and  from 

an  applied  voltage  of  approx.  200 V  onwards,  a 

vibrating  motor  is  put  in  rotation  inside  the  test 

probe  L2  .  With  the  voltage  increasing,  the 

speed of this motor is increasing as well.

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1   and L2   

only!  Do  not  cover  the  display  and  do  not  touch  the 

contact electrodes 

!

 

4.1  How to test the phase at AC voltage 

-   The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to AC 690 V! 

-   The  phase  test  is  possible  in  the  earthed  mains 

from 230 V onwards! 

-   Firmly grasp the handle of test probe L1  .

-   Place the contact electrode 

 of test probe L1   

against the relevant point of the unit under test.

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   If  the  “R”  symbol  appears  on  the  LC  display 

the  tester  is  in  contact  with  the  live  phase  of  an 

AC voltage on this point of the unit under test. 

Never touch the contact electrode of test probe L2 

during the single-pole test (phase test)!

Note: 

The  reading  of  the  LC  display 

  might  be  impaired 

due to unfavorable light conditions, protective clothing 

or in insulated locations. 

Attention:

The absence of voltage can be detected by means of 

a bipolar test only.

5.  How to test DC voltages 

-    The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30 seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly  grasp  the  insulated  handles    and    of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   For  AC  voltages  from  24 V  onwards  and  when 

pressing both push buttons (load test) from 12 V 

onwards, the LEDs “plus” and “minus” 

 and 

 

light up. Furthermore, all LEDs light until the step 

value of the applied voltage is reached. 

-   When  pressing  both  push  buttons 

  and  from 

an  applied  voltage  of  approx.  200 V  onwards,  a 

vibrating  motor  is  put  in  rotation  inside  the  test 

probe  L2  .  With  the  voltage  increasing,  the 

speed of this motor is increasing as well.

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1   and L2   

only!  Do  not  cover  the  display  and  do  not  touch  the 

contact electrodes 

!

5.1  How to test the polarity at DC voltage 

-   The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly  grasp  the  insulated  handles    and    of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   If LED 

 lights up, the “positive pole” of the unit 

under test is at test probe  .

-   If LED 

 lights up, the “negative pole” of the unit 

under test is at test probe  .  

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1   and L2    

only!  Do  not  cover  the  display  and  do  not  touch  the 

contact electrodes 

!

6.   How  to  test  the  phase  sequence  of  a  three-

phase mains

The required auxiliary voltage is provided by the power 

supply (2 x 1.5 V batteries) integrated into test probe 

L1  .  Check  the  functional  status  of  the  batteries 

before  measuring  by  activating  the  measuring  point 

illumination.

-   The  voltage  tester  must  be  used  only  within  the 

nominal voltage range of 12 V up to AC 690 V! 

-   The phase-sequence test is possible from 230 V 

AC  voltage  (phase  against  phase)  onwards  in  a 

earthed three-phase mains.

-   Firmly  grasp  the  insulated  handles    and    of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   The LEDs have to indicate the external conductor 

voltage. 

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   When  contacting  the  two  contact  electrodes 

  with  two  phases  of  a  three-phase  mains 

connected  in  clockwise  rotation,  the  LC  display 

 

indicates the “R” symbol. If for two phases the 

rotation  is  anti-clockwise,  no  symbol  appears  on 

the LC display.

The  phase-sequence  test  always  requires  a  counter-

test!  If  the  LC  display 

  indicates  clockwise  rotation 

for  two  phases  of  a  three-phase  mains,  those  two 

phases must be contacted again with reversed contact 

electrodes 

  during  the  counter-test.  There  must 

be no symbol indicated on the LC display during the 

counter-test.

 

If in both cases the LC display indicates 

the  „R“  symbol,  the  earthing  is  too  weak  or  the 

batteries are empty. 

Attention!

In  case  of  empty  batteries,  „R“  indication  for 

clockwise and anti-clockwise rotation! 

Note: 

The  reading  of  the  LC  display 

  might  be  impaired 

due to unfavorable light conditions, protective clothing 

or in insulated locations. 

7.   How  to  test  an  electrically  conductive 

connection (continuity check) 

-   The  continuity  check  must  be  performed  on 

the  relevant  points  of  a  “dead”  (not  being 

under  voltage)  unit  under  test.  If  necessary,  the 

capacitors must be discharged. 

-   The necessary test voltage is supplied by means 

of the power supply (2 x 1.5 V batteries) integrated 

in the test probe L1  . 

-   The  test  is  possible  within  the  range  of  

0 - 108 kΩ. 

-   Firmly grasp the handles L1   and L2  . 

-   Place  the  test  probes  L1    and  L2    with  the 

contact  electrodes 

  against  the  relevant  points 

of the unit under test. 

-   When  contacting  an  electrically  conductive 

connection  with  the  contact  electrodes 

,  the 

voltage  tester  gives  an  acoustic  signal  and  the 

signaling LED 

 lights up.

8.  Battery replacement

Do  not  set  the  voltage  tester  under  voltage  with  the 

battery compartment being open!

The energy supply for the phase-sequence indication, 

illumination  and  continuity  check  of  the  DUSPOL

®

 

expert is done by means of two built-in micro batteries 

(LR03/  AAA).  Battery  replacement  is  necessary  as 

soon  as  illumination  does  not  work  anymore.  In  this 

case, the battery voltage is below 2.2 V.

How to replace the batteries:

Take  a  screw  driver  and  open  the  battery 

compartment  (next  to  the  cable  outlet)  by  a  

¼-turn  in  direction  of  the  arrow  (counter-clockwise). 

The slot is now vertical and the battery compartment 

with the batteries can be removed.

Remove  the  discharged  batteries  from  the  battery 

compartment.  Insert  the  new  batteries  with  correct 

polarity  (see  marking)  into  the  battery  compartment. 

Put  the  battery  compartment  with  the  batteries  back 

onto  the  handle  and  lock  it  by  ¼-turn  in  clockwise 

direction  (slot  must  be  horizontal  and  the  marking 

points are opposite!). Make sure not to damage the O 

ring. If necessary, it has to be replaced.

Battery disposal:

Do  not  dispose  of  batteries  with  the  household 

garbage.  You  as  a  consumer  are  legally  obliged  to 

return  used  batteries.  You  can  return  used  batteries 

to  public  collection  facilities  in  your  community  area 

or  return  them  to  any  retail  outlet  selling  similar 

batteries. Avoid using batteries containing dangerous 

substances! 

9.   Technical data: 

-   Guideline for two-pole voltage testers: IEC 61243-3

-   Protection class: IP 64, IEC 60529 (DIN 40050)

 

 IP 64  means:  Protection  against  access  to 

dangerous  parts  and  protection  against  solid 

impurities, dustproof, (6 - first index). Splash proof, 

(4 - second index). Can also be used in case of 

precipitation.

-   Nominal voltage range: 12 V to AC 690 V/ DC 750 V 

-  Internal resistance, measuring circuit: 

 

220 kΩ, parallel 3.9 nF (1.95 nF)

-   Internal  resistance,  load  circuit  –  both  push 

buttons actuated!: approx. 3.7 kΩ...(150 kΩ)

-  Current consumption, measuring circuit: 

 

max. I

n

 3.5 mA (690 V) AC/ 3.4 mA (750 V) DC

-   Current  consumption,  load  circuit  -  both  push 

buttons actuated!: I

0.2 A (750 V)

-   Polarity indication: LED +; LED - 

 

(indicating handle = positive polarity)

-   Indicating steps LED: 12 V+*, 12 V-*, 24 V+, 24 V-, 

50 V, 120 V, 230 V, 400 V and 690 V (*: only with 

both push buttons actuated)

-   max. indicating errors:  U

n

 ± 15 %, ELV U

n

 

- 15 %

-   Nominal frequency range f: 0 to 60 Hz 

 

Phase and phase-sequence indication 50/ 60 Hz

-   Phase and phase-sequence indication: ≥ U

n

 

230 V

-   Vibrating motor, starting: ≥ U

n

 230 V

-   max. permissible operating time: ED = 30 s (max. 

30 seconds), 240 s pause

-   Test current, continuity check: max. 2 μA

-   Testing range, conducting resistance: 0 - 108 kΩ, 

-   Sound level acoustic signal: 55 dB

-   Measuring point illumination (in 30 cm): 10 Lux

-   Current consumption measuring point illumination: 

46 mA

-   Current consumption continuity check: 83 mA

-   Current  consumption  automatic  switch-on 

illumination: 23 mA

-   Battery: 2 x Micro, LR03/ AAA

-   Weight: approx. 200 g

-   Connecting cable length: approx. 900 mm

-   Operating  and  storing  temperature  range:  -10 °C 

to +55 °C (climate category N)

-   Relative  air  humidity:  20 %  to  96 %  (climate 

category N)

-   Reverse control times (thermal protection):

voltage

time

230 V

30 s

400 V

9 s

750 V

2 s

Attention! 

The  phase-sequence  indication,  measuring  point 

illumination and continuity check do not work anymore, 

if the batteries are empty!

Remove the batteries if not using the voltage tester for 

a longer period of time! 

10.  General maintenance:

Clean  the  exterior  of  the  housing  with  a  clean  dry 

cloth (exception: special cleansing cloths). Do not use 

solvents and/ or abrasives to clean the voltage tester. 

Make sure not to contaminate the battery compartment 

and  the  battery  contacts  with  leaking  battery 

electrolyte.  Should  such  electrolyte  contamination  or 

white  deposits  occur  near  the  battery  or  the  battery 

housing, these must also be removed with a dry cloth. 

In  case  of  wear  or  damaging  of  the  O  ring  of  the 

battery  compartment,  the  voltage  tester  does  not 

comply  with  the  indicated  protection  class  anymore 

(protection against dust and water). In this case, the O 

ring must be replaced.

The O ring can be ordered under the BENNING piece 

number 772897. Moisten a new O ring with glyzerin or 

talcum so that the battery compartment can be locked 

and unlocked easily.

11.   Environmental notice