BENNING MA 3 measuring adapter

 

 

 

6.2. Testing of extension cables 

6.2.1.  RPE – Protective conductor resistance 

Before testing 

 

 

The maximum testing current for RPE meas-
urement is 10 A

 

 

The rotary switch of the 
BENNING MA 3 can be 
used for RPE measure-
ment in any locking posi-
tion. 

 

 

Before starting the test, determine the internal 

RPE

  re-

sistance of the measuring adapter. 

Internal RPE resistance of the measuring adapter 

RPE – BENNING MA 3 

  Start the 

RPE

 measurement on your appliance 

tester. 

  Contact the test probe of the appliance tester with 

the PE contact of the corresponding CEE

 socket

 

(see figure “

RPE – BENNING MA 3

”). 

  Write down the measured 

RPE

 value. 

  Follow the test procedure 

Class I, RPE

 for “

porta-

ble test samples

”. 

 

 

The manufacturer recommends to write down 
the known measured RPE values of all CEE 
connections of the BENNING MA 3 for future 
measurements and add them to the measuring 
adapter. 

 

RPE – BENNING MA 3 (e. g. CEE 5-pin, 32 A) 

Setup for measuring the internal RPE resistance of the MA 3 

 

 

 

Connection diagram 

 

 

Detailed view 

 

Test procedure VDE 0701-0702 

 

Class I; RPE (e. g. CEE 5-pin, 32 A) 

Cable test 

 

  Connect both cable connections to the corresponding 

CEE sockets of the 

BENNING MA 3

  Connect the test probe of your appliance tester to the 

PE socket (see pos. 

1

, chapter 

4

) of the 

BEN-

NING MA 3

  Start the 

RPE

 measurement on your appliance tester. 

  Read the 

RPE

 measuring result shown on the display of 

the appliance tester. 

  Subtract the measured 

RPE

 value of the 

BENNING MA 

3

 from the 

RPE

 measuring result of the test sample.  

As a result, you will obtain the measured 

RPE

 value of the 

test sample. 

  Edit the measured 

RPE

 value in the appliance tester ac-

cording to the calculated measuring value. 

 

Application 

 

Class I; RPE (e. g. CEE 5-pin, 32 A) 

Cable test 

 

 

 

Connection diagram 

 

 

Detailed view 

 

 

Circuit diagram 

 
 

 

Summary of Contents for 044159

Page 1: ...BENNING MA 3 CEE Messadapter 5 3 polig Operating manual Translated version English 5076 en Version 1 00 19 February 2018...

Page 2: ......

Page 3: ...NG MA 3 3 6 1 Testing of three phase devices 3 6 1 1 RPE Protective conductor resistance 3 6 1 2 RInsu Insulating resistance 4 6 1 3 Alternative leakage current measurements 6 6 2 Testing of extension...

Page 4: ...more than one test sample or one extension cable at a time In case of proper use according to the specifications the safety of both the user and the device is ensured Please read the operating manual...

Page 5: ...V L N PE 6h 3 CEE connector 32 A 50 Hz to 60 Hz 380 V to 415 V 3L N PE 6h 4 Status LED indications CEE connector 3 pin 5 pin 5 Rotary switch for RInsu test alternative leakage current test functional...

Page 6: ...NNING MA 3 measuring adapter to the test socket of your appli ance tester Connecting the BENNING MA 3 Connecting the BENNING MA 3 to the appliance tester Connection diagram 6 Testing with the BENNING...

Page 7: ...est sample from the mains supply Switch the rotary switch of the BENNING MA 3 to the locking position L1 L2 L3 Test procedure VDE 0701 0702 Class I RInsu Portable test sample Connect the CEE connector...

Page 8: ...am Circuit diagram Class I RInsu secondary to PE Portable test sample Connection diagram Circuit diagram Class I RInsu LN to secondary Portable test sample Connection diagram Circuit diagram Class I R...

Page 9: ...d appliance tester IPE protective conductor current ICont contact current ILeak device leakage current IPLeak patient leakage current Before testing Disconnect the test sample from the mains supply Sw...

Page 10: ...on class II that raise concerns as to an RInsu measure ment Moreover it is checked to prove the proper insula tion capacity under mains voltage This also applies to de vices of protection class I with...

Page 11: ...t sample Application Class I IPLeak patient leakage current Portable test sample Connection diagram Circuit diagram Test procedure VDE 0751 1 Class II IPLeak patient leakage current Portable test samp...

Page 12: ...CEE connections of the BENNING MA 3 for future measurements and add them to the measuring adapter RPE BENNING MA 3 e g CEE 5 pin 32 A Setup for measuring the internal RPE resistance of the MA 3 Conne...

Page 13: ...ductor is affected Application Class I RInsu LN to PE Cable test Connection diagram Circuit diagram 6 2 3 Functional test and phase sequence test of cables Before testing The functional test and phase...

Page 14: ...C to 60 0 C Max relative humidity linearly decreasing non condensing 80 0 at 30 0 C 60 0 at 40 0 C Protection category IP 40 with the case being open IP 67 with the case being closed Dimensions W x D...

Page 15: ...areparts benning de General service requests Phone 49 2871 93 556 E mail servicerequests benning de Returns management Phone 49 2871 93 554 E mail returns benning de Training management Phone 49 2871...

Page 16: ...to the technical status at the time of printing Subject to technical changes No liability for printing errors Support helpdesk BENNING helpdesk team Phone 49 2871 93 555 Fax 49 2871 93 417 E mail info...

Reviews: