Troubleshooting
18
VAPOR LOCK
Vapor lock is a problem that results from ambient temperatures, vapor pressure of the product, and the installation. It is not a characteristic of a
pump.
REASONS FOR VAPOR LO CK
The
Atmospheric Pressure,
of 14.7 PSI (Seal Level) presses on the liquid in the tank
as shown in
Figure 18
.
Vapor Pressure
(the amount of pressure required to keep the product in a liquid
form at 60
F) of today’s product is approximately 10 PSI. See
Figure 19
.
The difference between
Atmospheric Pressure
and
Vapor Pressure
is known as the
Working Pressure
. The
Working Pressure
is all that the pump can create without
the product turning to vapor. To figure the Working Pressure take Atmospheric
Pressure minus the Vapor Pressure (i.e. Calculation: Atmospheric Pressure – Vapor
Pressure = Working Pressure) Refer to
Figure 20
.
Example:
14.7 - 10.0 = 4.7 PSI
Figure 18
Figure 19
Figure 20
10 PSI required to keep product
in liquid form
60°F
_
14.7 PSI Atmospheric Pressure
4.7 PSI Working Pressure
10.0 PSI Vapor Pressure at 60°F
_____
111
Summary of Contents for 111103
Page 4: ...Bennett T140 Operation Service Parts Manual Table of Contents ii Page Intentionally Left Blank...
Page 19: ...Bennett T140 Operation Service Parts Manual Troubleshooting 14 Figure 15...
Page 20: ...Bennett T140 Operation Service Parts Manual Troubleshooting 15 Figure 16...
Page 34: ...Bennett T140 Operation Service Parts Manual Parts 29 Page Intentionally Left Blank...
Page 35: ...Bennett T140 Operation Service Parts Manual 30 Page Intentionally Left Blank...