Bennett 621 Interconnection Box Instruction & Service Manual

 

Service Instructions

 

14 

HELPFUL PROGRAMMING HINTS 

The following contains basic communication programming procedures for a Bennett Pacific and Nucleus POS. It is 

EXTREMELY

 

important that all of the appropriate Bennett and OEM manuals be reviewed prior to operation. 

 

To enter Manager’s Mode enter the access code 

<2218>

 and press 

<ENTER>

 

To access a specific manager’s mode, enter the mode number and press the <

MODE>

 key. 

 

If multiple displays associated with the selected manager’s mode, press the <

DOWN ARROW KEY> 

to cycle between 

the displays.  

 

To exit a specific manager’s mode and return to the idle manager’s mode, press the 

CANCEL

 key. 

BENNETT PACIFIC PROGRAMMING 

In order to function properly, the following settings 

MUST

 be programmed at the dispenser to communicate with the Nucleus®. 

 

NUCLEUS PROGRAMMING  

In order for the Bennett dispensers to function properly, the correct settings must be made in the pump-programming window 
of the Nucleus system. Three settings in the “

Pump Options

” window will need to be programmed correctly in order for the 

dispensers to function. These settings are TYPE, PUSH TO START, and VALID POSITIONS. Other settings in this window will not 
inhibit dispenser operation. 

Note: 

Please refer to the appropriate Nucleus programming guide for complete programming 

instructions. 

PACIFIC CONFIGURATION 

DISPENSER TYPE 

PUSH-TO-START 

VALID POSITIONS / GRADE MAPPING 

Three Product Blender 

VRB 

None or Select Grade 

3-High Grade, 5-Blend, 7-Low Grade 

3+1 Blender 

VRB Plus 

None or Select Grade 

1-Diesel, 4-High Grade, 5-Blend, 6-Low Grade 

Three Grade Mixer 

MGD Uni-Hose 

None or Select Grade 

1-Grade A, 2-Grade B, 3-Grade C 

One Grade Non-Blender 

MGD Uni-Hose 

None or Select Grade 

1-Grade A 

Two-Grade Non-Blender 

MGD Multi-Hose 

None or Select Grade 

1-Grade A, 2-Grade B 

Three Grade Non-Blender 

MGD Multi-Hose 

None or Select Grade 

1-Grade A, 2-Grade B, 3-Grade C 

 

MODE 

DESCRIPTION 

SETTING 

NOTES 

21 

Communication Type 

3 = Generic Current Loop 

Display will read “

generic Loop

” 

22 

Dispenser Address 

Site Specific 

Set a unique address for each fueling position. The 
display will read “

Generic adr 

xx

” where “

 xx

 ” 

will be the current address for the specific fueling 
position. Each fueling position may have an address 
from 1-24. Each fueling position must be connected to 
the appropriate position on the 621 interface board. 
The 621 pools each channel on the board in search of 
the correct address. 

Example:

 Channel 1 on the 621 

supports address 1 & 2. Channel 2 on the 621 supports 
address 3 & 4 and so on. 

23 

Push-To-Start  

0 = Disabled 
1 = Enabled 

Menu code 23 controls if push-to-start is required. This 
mode 

must be

 programmed to match the push-to-start 

field within pump programming in the Nucleus. 

99 

Unit of Measure  

Unit of Measurement 

1 = Gallons 
2 = Liters 
3 = British Imperial Gallons 
 

Decimal Placement 

1 = 1000

th

  

This menu code sets the volume unit of measurement. 
Option 1 is for gallons, 2-Liters, 3-British Imperial 
Gallons. Press Enter to access decimal location. Option 
1 must be set to 1 (1000

th

) for operation with the 

Nucleus. 

08 

Decimal Location 

0 = U.S.A. 

This menu code controls the decimal placement of the 
monetary display values. This mode must always be set 
to option 0 for operation with the Nucleus. 

Summary of Contents for 104080

Page 1: ...ON BOX P N 115763 115VAC Fuel Positions 1 through 24 P N 104080 Fan Out Board Installation Service Manual 116186 Rev C 11 13 18 Only Trained Personnel May Work on This Equipment READ THIS MANUAL This...

Page 2: ...99 6202 Email sales bennettpump com or salesintl bennettpump com Website www bennettpump com For new manuals visit our web page at www bennettpump com IMPORTANT Examine the shipment immediately upon a...

Page 3: ...ions 3 Pump Controller Assembly 621 Box 4 SECTION 3 INSTALLATION INSTRUCTIONS 9 621 Interconnection Box Recommended Equipment and Materials 9 How To Mount the 621 Interconnection Box 9 AC Power Requir...

Page 4: ...Bennett 621 Interconnection Box Instruction Service Manual Table of Contents ii Page Intentionally Left Blank...

Page 5: ...authorized personnel only Warranty work may only be performed by Bennett certified technicians To prevent electric shock keep the electrical parts of the dispenser dry Electronic components are static...

Page 6: ...AUTHORIZED ALTERATION OF BENNETT PRODUCTS DANGER BEFORE PERFORMING ANY TYPE OF SERVICE TO THE DISPENSERS BE SURE TO SHUT OFF ALL ELECTRICAL SUPPLIES AND SECURE THEM IN THE OFF POSITION CLOSE ALL VALVE...

Page 7: ...id the Bennett technician to troubleshoot site occurrences The Fan Out Circuit Board provides additional terminal strips for RS485 Data Communication SPECIFICATIONS 621 Dimensions length x width x hei...

Page 8: ...el protocol 621 CIRCUIT BOARD ASSEMBLY For locations with 1 through 16 Fueling Points ITEM DESCRIPTION 1 Enclosure 2 Circuit Board Assembly 621 Generic Current Loop Adaptor 3 Circuit Board Assembly Fa...

Page 9: ...ser Each 621 Interconnection Box uses one 120V 50 60 Hz or 240V 50 60 Hz circuit for power Make sure the power source has the correct frequency and voltage JP1 CURRENT LOOP VOLTAGE The JP1 is a 3 pin...

Page 10: ...tive 23 24 Yellow negative 13 NOT USED Orange positive NOT USED Yellow negative 14 NOT USED Orange positive NOT USED Yellow negative 15 NOT USED Orange positive NOT USED Yellow negative 16 NOT USED Or...

Page 11: ...diagnostic purposes Note All switches must be in the ON position If one of the switches is in the OFF position the point of sale will not be able to communicate to the dispenser connected to that DATA...

Page 12: ...sition screw terminal strip provides a DATA negative connection for each debit credit terminal S1 S8 SWITCH Switches S1 S8 on the circuit board are used for diagnostic purposes Note All switches must...

Page 13: ...ction Box measures 12 x 12 x 4 The enclosure requires four mounting screws These four screws are on 10 by 10 centers Note When installing a 621 Interconnection Box pay attention to the locations of th...

Page 14: ...e and may void warranty Dispenser fuel communication wires for fueling positions 1 through 24 terminate directly to the 621 Circuit Board Each fueling point has a positive orange and negative yellow c...

Page 15: ...m occurs refer to the service and troubleshooting section for more information or call Bennett Technical Support at 1 800 423 6638 1 Apply power to dispensers program them for operation and address th...

Page 16: ...Bennett 621 Interconnection Box Instruction Service Manual Installation Instructions 12 CONNECTION DIAGRAM...

Page 17: ...T Red Generic Current Loop Transmit Fuel Controller D2 WR Red Generic Current Loop Receive Fuel Controller D3 BT Red Bennett Transmit Dispenser Communication D4 BR Red Bennett Receive Dispenser Commun...

Page 18: ...lender VRB Plus None or Select Grade 1 Diesel 4 High Grade 5 Blend 6 Low Grade Three Grade Mixer MGD Uni Hose None or Select Grade 1 Grade A 2 Grade B 3 Grade C One Grade Non Blender MGD Uni Hose None...

Page 19: ...lt equivalent All rebuilt boards have a part number prefix of RB You must use factory rebuilt parts for all warranty service work Please refer to the Distributor Policy Manual for program terms and de...

Page 20: ...Bennett 621 Interconnection Box Instruction Service Manual Parts 16 Page Intentionally Left Blank...

Page 21: ...Bennett 621 Interconnection Box Instruction Service Manual Bennett Limited Warranty...

Page 22: ...Bennett 1218 E Pontaluna Road Spring Lake MI 49456 USA 800 235 7618 Outside USA 231 798 1310 sales bennettpump com www bennettpump com...

Reviews: