P-9000LT/F Low-Rise Pit Lift
36
P/N 5900022 — Rev. B — Nov. 2019
To connect to a 208-240 VAC power source
:
1.
Remove the front of the Console if it is currently in place. You need to access the Power Unit.
2.
Locate the Pigtail coming out of the Electrical Box on the Power Unit.
3.
Open the Electrical Box, note where each wire is connected, remove the Pigtail, and then either:
–
Wire the Power Unit directly into the facility’s electrical system,
or
–
Wire a power cord with appropriate plug starting inside the Electrical box where the Pigtail was
wired.
You can find the Wiring Diagram for your Power Unit in
4.
Close the Electrical Box.
5.
If you wired a power cord with plug, plug it in to an appropriate power outlet.
Install a Power Disconnect Switch
⚠
WARNING
A Power Disconnect Switch is
not
provided with this equipment.
A Power Disconnect Switch is a National Electrical Code (NEC) requirement. They are designed to
interrupt main electrical power in the event of an electrical circuit fault, emergency situation, or when
equipment is undergoing service or maintenance.
Make sure to install a Power Disconnect Switch that is properly rated for the incoming power source.
Your Power Disconnect Switch must be installed so that it is in
easy reach of the Operator
or in
their line of sight. The Power Disconnect Switch must be
clearly marked
to indicate its purpose.
If you are not clear where to put the Power Disconnect Switch, consult with your Electrician.
⚠
DANGER
Installing a Thermal Disconnect Switch
must
be performed by a licensed, certified
Electrician.
Have the Electrician select a
UL-listed
Power Disconnect Switch.
Install a Thermal Disconnect Switch
⚠
WARNING
The motor on the Power Unit has
no thermal overload protection
.
Have the Electrician connect a motor Thermal Disconnect Switch or overload device that will make
sure the equipment shuts down in the event of an overload or an overheated motor.
⚠
DANGER
Installing a Thermal Disconnect Switch
must
be performed by a licensed, certified
Electrician. Do not perform
any
maintenance or installation on the Lift without first
making sure that main electrical power has been disconnected from the Lift and
cannot
be re-energized until all procedures are complete.
High running amps that exceed the motor’s full load amps (FLA) rating may result in permanent
damage to the motor.
Do not exceed the rated duty cycle of the motor.
Summary of Contents for P-9000LT
Page 50: ...P 9000LT F Low Rise Pit Lift 50 P N 5900022 Rev B Nov 2019 Wiring Diagrams 5585020 5585015 ...
Page 52: ...P 9000LT F Low Rise Pit Lift 52 P N 5900022 Rev B Nov 2019 Labels ...
Page 53: ...P 9000LT F Low Rise Pit Lift 53 P N 5900022 Rev B Nov 2019 ...
Page 54: ...P 9000LT F Low Rise Pit Lift 54 P N 5900022 Rev B Nov 2019 ...
Page 55: ...P 9000LT F Low Rise Pit Lift 55 P N 5900022 Rev B Nov 2019 Parts Diagrams ...
Page 56: ...P 9000LT F Low Rise Pit Lift 56 P N 5900022 Rev B Nov 2019 ...
Page 57: ...P 9000LT F Low Rise Pit Lift 57 P N 5900022 Rev B Nov 2019 ...
Page 58: ...P 9000LT F Low Rise Pit Lift 58 P N 5900022 Rev B Nov 2019 ...
Page 59: ...P 9000LT F Low Rise Pit Lift 59 P N 5900022 Rev B Nov 2019 ...
Page 60: ...P 9000LT F Low Rise Pit Lift 60 P N 5900022 Rev B Nov 2019 ...
Page 61: ...P 9000LT F Low Rise Pit Lift 61 P N 5900022 Rev B Nov 2019 ...
Page 62: ...P 9000LT F Low Rise Pit Lift 62 P N 5900022 Rev B Nov 2019 ...
Page 63: ...P 9000LT F Low Rise Pit Lift 63 P N 5900022 Rev B Nov 2019 Maintenance Log ...