background image

T M

Document NAE1038020   

•   

10.2012   

•   

©  Bender Inc.   

•   

Page 1/1   

•   

Side 1/2

Bender Inc.   

•   

USA: 800.356.4266  /  610.383.9200  /  [email protected]   

•   

Canada: 800.243.2438  /  905.602.9990  /  [email protected]   

•   

www.bender.org

VMD420

Installation Bulletin / Reference Guide

This document is intended as a reference guide for installing and using a BENDER VMD420 three-

phase voltage and frequency monitor.  This document includes installation, setup, and usage instruc-

tions. For complete details, including installation, setup, settings, and troubleshooting, refer to the 

VMD420 user manual, document number TGH1396en. This document is intended as a supplement 

and not a replacement to the complete user manual.

Only qualified maintenance personnel shall operate or service this equipment. These instructions 

should not be viewed as sufficient for those who are not otherwise qualified to operate or service this  

equipment. This document is intended to provide accurate information only. No responsibility is as-

sumed by BENDER for any consequences arising from use of this document.

Installation

Mounting

VMD420 series devices may be DIN rail mounted, or screw mounted using the black clips lo-
cated on the top and bottom of the device. Screw mounting requires an extra black clip (article 
number B98060008, sold separately).

! DANGER

• Disconnect all power before servicing.

• Observe all local, state, and national

  codes, standards, and regulations.

HAZARD OF ELECTRIC SHOCK,

EXPLOSION, OR ARC FLASH

Wiring - General

Refer to figure 1 for wiring the VMD420.  Use minimum 
AWG 24, maximum AWG 12 size wire. Refer to VMD420 
series user manual for complete technical details.

1.  External supply voltage; 5A fuse 

required for internal device pro-
tection

2.  System connections (N connec-

tion is only necessary when N is 
being used)

3.  Alarm relay K1: SPDT contact
4.  Alarm relay K2: SPDT contact

Figure 1 - VMD420 wiring diagram

Front Panel Display

1.  LED “ON” (green): Illuminates when 

power is applied to the device. Flashes 
when the CT connection alarm is active.

2.  LED “AL1” (yellow): Illuminates when 

the prealarm is activated. Flashes when 
the CT connection alarm is active.

3.  LED “AL2” (yellow): Illuminates when 

the main alarm is activated. Flashes 
when the CT connection alarm is active.

4.  Backlit LCD display

5.  TEST / UP button: Activates self-test / 

scrolls up inside main menu.

6.  RESET / DOWN button: Resets device / 

scrolls down inside main menu.

7.  MENU / ENTER button: Activates main 

menu / Confirms (momuntary push) or 
goes back a step (held > 1.5 s) inside 
main menu.

1

2

3

4

5

6

7

Figure 2 - VMD420 front display

1

2

3

4

Menu Flow Chart for Common Settings

Figure 4 through figure 8 on the reverse side of this document contain flow charts for modify-
ing commonly used features and settings in the VMD420’s main menu. Not all available fea-
tures are listed in this document. For more information, consult the VMD420 user manual.

R

T

Menu Legend

MENU / ENTER button

DOWN ARROW button

UP ARROW button

Momuntary button push

< 1.5 s

Hold button for at least 1.5 s, 
then release

> 1.5 s

Wiring - Contacts

Using a normally closed or normally open contact utilizes two factors: wiring out of the proper 
terminal, and setting the respective contact to normally energized or deenergized operation. 
Refer to the chart below for relay conditions. For changing the energized state of the contact, 
refer to “Figure 7 - Contact operation” on the reverse side of this document.

The factory default for the VMD420 is normally energized operation for relay K2, and normally 
deenergized operation for relay K1.

Dimensions

Dimensions in inches (mm).

1.42” (36)

2.78”

(70.5)

1.87”

(47.5)

1.22” (31.1)

2.66” (67.5)

1.77” (45)

3.54” (90)

Normally energized mode (N/E)
Failsafe mode
“N/C” in device settings menu

Energized in the normal state

Relay will switch when the alarm is
activated, or when supply voltage
to the device is lost.

Power ON, normal state (no alarms)

Power OFF

Power ON, alarm state

11-12 OPEN
11-14 CLOSED

11-12 CLOSED
11-14 OPEN

11-12 CLOSED
11-14 OPEN

21-22 OPEN
21-24 CLOSED

21-22 CLOSED
21-24 OPEN

21-22 CLOSED
21-24 OPEN

Normally deenergized mode (N/D)
Non-failsafe mode
“N/O” in device settings menu

Energized in the alarm state

Relay will switch when the alarm is
activated.

Power ON, normal state (no alarms)

Power OFF

Power ON, alarm state

11-12 CLOSED
11-14 OPEN

11-12 CLOSED
11-14 OPEN

11-12 OPEN
11-14 CLOSED

21-22 CLOSED
21-24 OPEN

21-22 CLOSED
21-24 OPEN

21-22 OPEN
21-24 CLOSED

Relay Operation Setting

Device Alarm State

K1 STATE

K2 STATE

Device Relay Conditions

Reviews: