9. Technical data
9.1 Technical data BM800/BM400 modules
Insulation coordination according to IEC 60664-1
Rated insulation voltage........................................................................................................................................ AC 250 V
Rated impulse voltage/pollution degree ................................................................................................................ 4 kV/3
Voltage supply TM800 .................................................... via integrated power supply unit, data depending on the type
BM800 module
Supply voltage
U
s
.............................................................................................................................................. AC/DC 24 V
Frequency range
U
s
............................................................................................................................... AC 40…60 Hz/DC
Operating range
U
s
...................................................................................................................AC 18…28/DC 19…30 V
The length of time the device can function in the event of a power failure: time, date..................................... > 5 days
Restart in the event of voltage failure for at least.........................................................................................................1.5 s
Display, characters....................................................................................................................four lines, 4 x 20 characters
Standard message texts in ...............................................................................................................21 national languages
Alarm addresses ........................................................................................................................................................≤ 250
Text messages, programmable....................................................................................................................................1000
History memory (messages)........................................................................................................................................1000
Standard text message..............................................................................................................................3 x 20 characters
Additional text message (press button to access) ...................................................................................3 x 20 characters
Alarm LEDs (three different colours) green (normal), yellow (warning), red (alarm)
Menu texts..................................................................................................................................................German/English
Buttons.......................................... 5 (lamp test + test of assigned devices, buzzer mute, additional text, scroll, menu)
Power consumption ................................................................................................................................................ ≤ 5 VA
Buzzer
Buzzer message ............................................................. can be acknowledged, adoption of characteristics of new value
Buzzer interval .................................................................................................................................................configurable
Buzzer frequency .............................................................................................................................................configurable
Buzzer repetition configurable
Interface internal/external
Interface/protocol............................................................................. 1 x RS-485/BMS internal, 1 x RS-485/BMS external
Baud rate............................................................................................ 9.6 kbit/s internal, 19200…57600 kbit/s external
Cable length ........................................................................................................................................................ ≤ 1200 m
Cable: twisted pair, one end of shield connected to PE: J-Y(St)Y min. 2x0.8
Terminating resistor ............................120 Ω (0.25 W) can be connected via DIP switch, factory setting: "off" position
Device address, BMS bus external/internal ............................................................................................ 1…150/1…99
Factory setting device address internal/external ............................................................................1 (master)/1 (master)
Programming
Interfaces ................................................................ RS-485 or USB (V2.0/V1.1), USB cable: Type A plug on Type B plug
Software...............................................................................................................................TMK-SET version 4.x or higher
Factory setting password query............................................................................................................................ activated