
Operation
63
RCMS460-490_D00067_03_M_XXEN/12.2017
Resolution of settings
type A
(RCMS…-D4/-L4 only, channels k9…k12):
Setting range
Resolution of setting
100…200 mA
10 mA
250…500 mA
50 mA
600 mA… 2 A
100 mA
2.5 A…5 A
0.5 A
6 A…20 A
1.0 A
25 A…50 A
5.0 A
60 A…125 A
10.0 A
Resolution of settings
type Flex
.: the same as for type A
3. Function
Monitoring the measuring channel for overcurrent or undercurrent. Use of the
measuring channel as digital input. Unused measuring channels have to be
disabled.
>
Alarm when the response value is exceeded.
<
Alarm when the value falls below the set response value.
0/1
Use of the measuring channel as digital input.
off
Measuring channel disabled.
* Scanning time digital inputs < 3.5 s.
Potential-free contact > 250 Ω, LC display indication: "0"
Potential-free contact < 100 Ω LC display indication: "1"