![Bender RCMB103 Operating Manual Download Page 20](http://html1.mh-extra.com/html/bender/rcmb103/rcmb103_operating-manual_2731523020.webp)
Technical data
20
RCMB103_D00044_00_M_XXEN/08.2013
Environmental conditions
Without solar radiation, precipitation, water, icing. Condensation possible temporarily:
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3).................................................................................................................................... 3K5
Transport (IEC 60721-3-2) ........................................................................................................................................... 2K3
Long-time storage (IEC 60721-3-1) ............................................................................................................................ 1K4
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................................................................................... 3M6
Transport (IEC 60721-3-2) ......................................................................................................................................... 2M2
Storage (IEC 60721-3-1) ............................................................................................................................................ 1M3
Deviation from the classification of climatic conditions:
Ambient temperature, during operation ............................................................................................... -25 °C…+80 °C
Ambient temperature, during transport ............................................................................................... -40 °C…+80 °C
Ambient temperature, during long-time storage ................................................................................. -25 °C…+80 °C
Relative humidity ...............................................................................................................................................10…90 %
Air pressure.................................................................................................................................................... 70…106 kPa
Connection
Plug-in connectors for PCBs, single-row .......................................................................................... 0.65 mm x 0.65 mm
Possible counterpiece for plug-in connector ............................................................................. Samtec: BCS-104-L-S-TE
......................................................................................................................................................... 3M: 960104-6202-AR
Modular dimensions ............................................................................................................................................ 2.54 mm
Other
Operating mode ................................................................................................................................continuous operation
Position of normal use ...................................................................................................................................................any
Software version......................................................................................................................................................D396 V1
Weight ......................................................................................................................................................................≤ 65 g
4. 2 Ordering information
Type
Measuring
range
Art. No.
RCMB103
0…6 mA DC
B 9404 2105