Function
17
RCMA420-DM_D00060_02_M_XXEN/06.2016
3.2.6
Start-up delay
t
After connection to the supply voltage
U
S
, the alarm indication is delayed by
the preset time
t
(0…10 s).
3.2.7
Residual current monitoring in window discriminator
mode
Change the measuring principle by selecting the window mode (SEt / In). In
the window discriminator mode, the threshold values I1 and I2 represent the
upper and the lower value. If the measured value is not within this area, an
alarm is initiated by the device. See page 30.
3.2.8
Password protection (on, OFF)
When the password protection is activated (on), settings are only possible af-
ter entering the correct password (0…999).
3.2.9
Factory setting FAC
After activating the factory setting, all settings previously changed are reset to
delivery status.