Application/inputs and outputs
47
PEM533_D00013_00_M_XXEN/06.2015
The maximum demand value determined over the whole recording period (peak
demand) will be stored and displayed. The peak demand can be reset manually.
Setting possibilities See “Setup: possibilities” on page 40.
7.5 Setpoints
The device supports two different types of setpoints:
1. Control setpoints for the general control applications and alarming.
2. Setpoints of the digital inputs and outputs: Provides control output actions in
response to changes in digital input status.
7.5.1 Control setpoints
The device features 9 user programmable control setpoints which provide exten-
sive control by allowing a user to initiate an action in response to a specific condi-
tion. The alarm symbol
at the bottom of the LC display is lit if there are any
reached/active control setpoints.
Setpoints can be programmed via the
communications interface.
The following
setup parameters
are provided:
1.
Setpoint type:
Specifies the monitoring condition (over setpoint or under set-
point) or is deactivated.
2. Setpoint parameter
Table 7.1: Setpoint parameters
Key Parameters Factor; Unit Key Parameters Factor; Unit Key Parameters Factor; Unit
0
—
—
6
λ
ges
x1,000
12
TOHD
I
x10,000
1
U
LN
x 100; V
7
THD
U
x10,000
13
Demand
P
ges
x 1,000; kW
2
U
LL
x 100; V
8
THD
I
x10,000
14
Demand
Q
ges
x 1,000;
kvar
3
I
x 1000; A
9
TEHD
U
x10,000
15
Demand
S
x 1,000; kVA
4
P
ges
x 1,000; kW
10
TEHD
I
x10,000
16
Ø Demand
I
x 1,000; A
5
Q
ges
x 1,000;
kvar
11
TOHD
U
x10,000
Summary of Contents for PEM533
Page 24: ...Installation and connection 24 PEM533_D00013_00_M_XXEN 06 2015...
Page 86: ...Modbus Register Map 86 PEM533_D00013_00_M_XXEN 06 2015...
Page 90: ...Technical data 90 PEM533_D00013_00_M_XXEN 06 2015...
Page 93: ...INDEX 93 PEM533_D00013_00_M_XXEN 06 2015...
Page 94: ......
Page 95: ......