LIM2010

Installation Bulletin / Reference Guide

This document is intended as a reference guide to installing and setting a BENDER LIM2010 Line Isola-

tion Monitor. This document includes installation instructions and typical front plate display indica-

tions of the device. For complete details, including installation, setup, settings, and troubleshooting, 

refer to the  LIM2010 user manual.

Only qualified maintenance personnel shall operate or service this equipment. These instructions 

should not be viewed as sufficient for those who are not otherwise qualified to operate or service this  

equipment. This document is intended to provide accurate information only. No responsibility is as-

sumed by BENDER for any consequences arising from use of this document.

Installation

Mounting

The front plate provides four holes with a diameter of 1/8” (3.2 mm) for screw mounting. Use 
the four (4) provided screws for mounting. Use minimum 2.6 lb-in (0.3 N-m), maximum 3.5 lb-
in (0.4 N-m) torque. Before mounting, plug the connector plate into the LIM. Refer to Figures 1 
and 2 for dimensions, listed in inches (mm).

Wiring

The LIM2010 connects to a connector plate assembly. Use the proper wiring diagram to con-
nect to the assembly. Before mounting the LIM, plug the connector plate into the LIM.

Figure 4 shows wiring the connector plate for basic in-
stallation with no accessories. If other equipment is to 
be installed, such as remote indicators, fault location, or 
load monitoring, or for more information on the con-
nector plate and installation, refer to the LIM2010 user 
manual.
Connector plate L1 and L2 connect to the main lines 
of the system, on the secondary of the isolation trans-
former. Connector plate LIMGND and GND2 are 

sepa-

rate

 connections to the system ground.

! DANGER

• Disconnect all power before servicing.

• Reference NFPA 99 / CSA Z32 for

  Installation Standard.

HAZARD OF ELECTRIC SHOCK,

EXPLOSION, OR ARC FLASH

4”

 (101.5)

7” (177)

6.5” (164)

4.4”

 (112)

5.3”

 (134.5)

2.4”

 (62)

3.1”
 (79.5)

Figure 1 - LIM2010 dimensions, front view

Figure 2 - LIM2010 dimensions, rear isometric view

Figure 3 - Connecting connector plate plugs to LIM2010

L1

L2

GND

Figure 4 - LIM2010 connector plate wiring - basic installation with no accessories

Connector Plate

Actual cable length for connector cables is 20” (50.8 cm). Both plugs are connected to 
LIM2010. Connector plate must only be installed in a grounded, metallic enclosure.

Figure 5 - CP-LIM2010 connector plate

Connector plate terminals

Type

Description

L1, L2

Connected to secondary of isolation transformer

12 VDC Com.

Common connection for remote indicators

A, B

RS-485 communication interface

RI1

Test button source for remote indicators

K1/NC

Alarm relay K1, N/C

K1/Common

Alarm relay K1, common

K1/NO

Alarm relay K1, N/O

SAFE

"SAFE" light connection for remote indicators

HAZARD

"HAZARD" light connection for remote indicators

RI2

Local and system muting from LIM and remote indicators

GND2, LIM GND

Separate ground connections

TEST

Connection for remote test

Z1/M+, Z2/M-

Connection for overtemperature sensor or analog meter

K2/Common

Alarm relay K2, common

K2/NC

Alarm relay K2, N/C

K2/NO

Alarm relay K2, N/O