1.1  Intended use

The Line Isolation Monitor (LIM) calculates the total hazard 
current in a single phase or three phase isolated power 
system. This is the maximum current that could flow through 
a person who made contact between an isolated conductor 

and ground.
Two seperate ground connections are provided for added safety 
when wiring the LIM into an isolated power system. Each ground 
should be wired individually to the reference grounding bus. A break 
in either connection will cause the LIM to alarm (flashing red LED).
Any other use, or any use beyond the foregoing, is deemed to be 
improper. The BENDER companies shall not be liable for any loss 
and damaging arising therefrom.
Correct use also includes
•    compliance with all instructions from the operating manual
•    adherence to any inspection intervals.
As a basic principle, our “General conditions of Sale and Delivery“ 
shall apply. These are available to the operator not later than the 
time when the contract is concluded.
1.2   Warranty and liability
Warranty and liability claims in the event of injury to persons or 
damage to property are excluded if they can be attributed to one or 
more of the following causes:
•    Improper use of the LIM.
•    Improper assembly/fitting, commissioning, operation and 
     maintenance of the LIM.
•    Failure to take note of the operating instructions concerning 

transportation, commissioning, operation and maintenance of 
the LIM.

•    Unauthorized structural modifications to the LIM.
•    Failure to take note of the technical data.

4

5

1. Safety Information

Summary of Contents for LIM2000plus LIM2000-1

Page 1: ...TGH 1337 Edition 01 06 Operating Manual LIM2000plus Line Isolation Monitor LIM2000 1 LIM2000 1CB LIM2000 3CB...

Page 2: ...r LIM2000 1 LIM2000 1CB and LIM2000 3CB 6 1 6 Inspection transport and storage 7 1 7 Important 7 1 8 Explanation of symbols and notes 8 1 9 Directives for installation 9 2 General Information 11 2 1 T...

Page 3: ...ing arising therefrom Correct use also includes compliance with all instructions from the operating manual adherence to any inspection intervals As a basic principle our General conditions of Sale and...

Page 4: ...evertheless when it is being used hazards may occur to the life and limb of the user or of third parties or there may be adverse effects on the LIM or on other valuable property The LIM must only be u...

Page 5: ...means a possible dangerous situation Failure to comply with these warnings means that slight physical injury or damage to property may ensue if the relevant precautions are not taken This symbol gives...

Page 6: ...he mute button comes on to indicate a muted condition Activating the test button starts the following procedures Audible alarm check Illumination of the analog LED bargraph Illumination of the 7 segme...

Page 7: ...nsformer current After setting the parameters they are stored and after leaving the menu the LIM performs a new self test 12 13 2 General Information 2 General Information 1 Amber THC setting LEDs ind...

Page 8: ...u and store new parameters menu END TEST 2 4 Error Codes Listing ER 1 0 Ground error LIM GNDor GND interrupted ER 2 0 AD converter calibration failed hardware failed error ER 3 0 Measuring circuit tes...

Page 9: ...icator and the isolated power supply are made via this cable assembly designed for integration into panels headwalls and other equipment The terminal strip works best with 18 ga wire The multiconducto...

Page 10: ...harness has a length of 20 2 5 1 Remote Indicator The MK2000 Remote Indicator series permanently mounts into standard one to xxx gang electrical boxes Low voltage wiring connects them via the connecto...

Page 11: ...s based on the superimposition of a measuring signal on the isolated power system The signal is very small and near the frequency of the power line making it compatible with all electrical equipment d...

Page 12: ...DC 200mA contact Rated contact voltage 250 V AC 24VDC Make capacity 4A AC 4A DC Break capacity at 24 V DC and L R 0 4 A Switching life 220 V AC 60 Hz 2 x 105 cycle Operation mode continuous LIM overl...

Reviews: