13. Alarm messages
Alarm message
Description
Measures
Reference
LED indicators
Check E-KE connections
for interruptions!
No low-resistance connection between terminals E and
KE to earth (PE)
• Check the wiring of terminals E and KE to earth (PE)
• Press the test button
ALARM 1 + ALARM
2 flash in common
mode
Service mode active!
The device is in maintenance condition
• Contact Bender Service
SERVICE lights up
No DHCP server found!
Connection problem at the Ethernet interface
• Check cable connection at the Ethernet interface
• Check the DHCP server's availability
• Check the DHCP's interface configuration in the device
Check time and date!
Time and date have not been set yet
• Set local time and date
(in case of voltage failure a buffer for three days)
Load on X1 too high!
Sum of the external loads on X1 is too high
• Check load at X1.+, X1.Q1 and X1.Q2
• Check ambient temperature
Device error x.xx
Internal device fault
• Press the TEST button
• Switch the supply voltage off and on
• Contact Bender Service
SERVICE lights up