4. Connection
IRDH575 has plug-in terminals.
Connect the terminals A1/+ and A2/- to the supply voltage
U
S
in accordance
with IEC 60364-4-43. The connections to the supply voltage shall be provided
with protective devices to afford protection in the event of a short-circuit (a 6
A fuse is recommended).
For UL and CSA applications, the use of 5 A fuses is mandatory.
Devices for protection against short-circuit in conformity with
IEC 60364-4-43 for the IT system coupling L1/L2/L3 can be omitted if the wi-
ring is carried out in such a manner as to reduce the risk of a short-circuited to
a minimum (a short-circuit-proof and earth-fault-proof wiring is recommen-
ded).
Use the accompanying terminal covers for terminal protection.
Only
qualified personnel
are permitted to carry out the
work necessary to install, commission and run a device or
system.
Risk of electrocution due to electric shock!
Touching live parts of the system carries the risk of:
An electric shock
Damage to the electrical installation
Destruction of the device
Before installing and connecting the device
,
make sure
that the
installation
has been
de-energised
. Observe the
rules for working on electrical installations.
DANGER