Function
58
6.6 Requesting device-specific information
6.6.1 Requesting fault messages after a self test
Writing to
FTC470XMB (= output data of the Modbus RTU Master)
Table 6.55: Master request: fault messages after a self test
Reading from
FTC470XMB (= input data of the Modbus RTU Master)
Table 6.56: FTC reply to: fault messages after a self test
When the FTC470XMB works in the BMS Slave mode, a temporary Master take-
over is required before carrying out the parameterization below!
Take into consideration that the Master function must be returned by the
FTC470XMB after Master function transfer and the parameterization.
Function
Devices
Word 2
Word 3
Word 4
Word 5
BMS
address
Chann
el No.
„0“
BMS
comma
nd
„0“
Data
type
Data
value
Request for fault messages after a self test
all
address
chan-
nel No.
0
9
0
1
0
No fault detected
EDS..,
RCMS....
Address
1... 12
0
9
0
1
0
Input not connected, no CT connected
EDS..,
RCMS....
„
1... 12
0
9
0
22
0
No CT connected
EDS..,
„
1... 12
0
9
0
22
0
Input switched off
EDS..,
RCMS....
„
1... 12
0
9
0
21
0
Input short-circuited
EDS..,
RCMS....
„
1... 12
0
9
0
23
0
No more channels
EDS..,
RCMS....
„
1... 12
0
9
0
254
254
Invalid value
EDS..,
RCMS....
„
1... 12
0
9
0
255
255