![Bender COMTRAXX MK2430 Manual Download Page 31](http://html1.mh-extra.com/html/bender/comtraxx-mk2430/comtraxx-mk2430_manual_2731600031.webp)
Installation and connection
31
MK2430_D00129_02_M_XXEN/09.2019
Example 1: Operating theatre or intensive care unit with two IT systems and
three rooms
Device
Parameter
Address settings
First UMC107E changeover and monitoring module
107TD47
Bus address
3
PRC487
Bus address
4
Second UMC107E changeover and monitoring module
107TD47
Bus address
5
PRC487
Bus address
6
Alarm indicator and test combinations
First
MK2430…
Bus address
1
Test address
3, 5
Alarm address
2, 3, 4, 5, 6, 7
Second
MK2430…
Bus address
2
Test address
3, 5
Alarm address
1, 3, 4, 5, 6, 7
Third
MK2430…
Bus address
7
Test address
3, 5
Alarm address
1, 2, 3, 4, 5, 6
m
ed
. gases