Display CP305: Menu structure
10.5
Settings
The settings of the CP305 are displayed here. You can adjust some device settings directly on the
device if you log in.
Changed settings are highlighted in yellow. The changes are confirmed (green tick) or discarded
(red X) in the header. You can make several changes at the same time on a single page. A pop-up
window prevents you from leaving the page with unsaved changes.
Digital inputs (for CP305-IO only)
Make settings for digital inputs IN1…12. Settings can be made channel by channel.
Mode
•
Off
•
High-active
•
Low-active
t(on)
•
The response delay indicates the delay with which the alarm is signalled.
•
Setting range 0…600 s
t(off )
•
The switch-off delay indicates how long an alarm needs to no longer be present before
the message is also cancelled.
•
Setting range 0…600 s
Relay (for CP305-IO only)
Carry out operating principle and function for relays 1…2.
•
Test Isometer (relay switches for approx. 30 seconds when a test of the assigned devices
(insulation monitoring devices, LIM, GFCI) is triggered using the “TEST” button).
•
Alarm addresses
•
Buzzer (the relay switches as soon as the buzzer sounds. In this way, other signalling
devices can be installed to indicate pending messages on the CP305.)
•
N/C and N/O operation
36
CP305_D00425_00_M_XXEN_09.2022