Operation and configuration
32
CMD420_421-DM_D00224_01_M_XXEN/08.2016
Parameter settings
An example is given below on how to change the alarm response value for
overcurrent > I1. It is presumed that the option overcurrent (HI) has been se-
lected in the SEt/I menu (factory setting). Proceed as follows:
1. Keep the "MENU / Enter" button pressed for more than 1.5 seconds.
The flashing short symbol AL appears on the display.
2. Confirm with Enter. The parameter response value I2 flashes, in addi-
tion the associated overcurrent value appears.
3. Use the Down button to select the parameter response value I1. The
parameter I1 flashes, in addition the associated percentage value for
prewarning of I2 appears.
4. Confirm with Enter. The current value for prewarning appears on the
flashing display.
5. Use the Up or Down button to set the appropriate prewarning value.
Confirm with Enter. I1 flashes.
6. You can exit the menu by:
– pressing the Enter button for more than 1.5 seconds to reach the
next higher level or
– selecting the menu item ESC and confirming with Enter to reach the
next higher level.
5.5.2
Changeover from overcurrent to undercurrent mode or to
window mode
The operating mode can be set in the SEt/I12 menu using the parameters HI,
Lo and In. By default, overcurrent operation (HI) is set. Refer to page 36 for a
detailed description on how to change over to the window mode.
The currently active segments of the display which can be
configured are flashing! These segments are highlighted by
an oval in the illustrations below. Press and hold down the
"MENU button" > 1.5 s to enter menu mode.