Data access using Modbus/TCP protocol
27
COM461MT_D00011_00_M_XXEN/05.2013
6.4
Structure of the exception code
6.5
Modbus address structure for BMS devices
Byte 9, 10
Value register 0
0x1234 (fictitious value)
Byte 11, 12 Value register 1
0x2345 (fictitious value)
Byte Name
Example
…
…
…
Byte 7
MODBUS function code
0x84
Byte 8
Exception code
0x01 or 0x02
Function
Address range
Number of
bytes
Number of
words
Device name
0x00…0x09
20 bytes
10 words
Timestamp
0x0A…0x0D
8 bytes
4 words
Common alarm
0x0E
(high byte)
1 byte
0.5 words
No BMS bus
connection
0x0E
(low byte)
1 byte
0.5 words
Not used
0x0F
2 bytes
1 word
Channel 1…32
0x10…0x8F
32 x 8 bytes
128 words
Alarm and test
Channel 33…64
0x90…0xFC
218 x 8 bytes
109 words
Byte Name
Example