Power Quality
61
PEM735_D00084_00_M_XXEN/02.2015
7.3.9
Swell Overvoltages
Voltage swells are typically caused by switching operations and load disconnections.
The nominal supply voltage
U
n
is used as reference. The swell start threshold is equal to
110 % of
U
n
, the hysteresis is 2 %.
In addition to the threshold, the duration of the voltage swell is also determined.
Voltage swells can trigger up to two of the following:
Relay outputs
Digital outputs
PQ-Log
Waveform recorder
Data recorder
Fig. 7.20: Voltage swells (subpage1)
These settings can only be made via the communication interface.
For detailed information refer to the annex "Modbus".