Benchmark 1500 - 2000 Boilers
APPENDIX A – BOILER MENU DESCRIPTIONS
Page
116
of
184
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0097_0C
Ph.: 800-526-0288
GF-142
Appendix A: Boiler Menu Item Descriptions – Continued
MENU LEVEL & OPTION
DESCRIPTION
SETUP MENU
Password
Allows password to be entered.
Once the valid password (159) is entered, options in
the Setup, Configuration and Tuning Menus can be
modified.
Language
Permits selection of English, Spanish or French for
displayed messages. Default is English.
Time
Displays time from 12:00 am to 11:59 pm.
Date
Displays dates from 01/01/00 to 12/31/99
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is
°F.
Comm Address
For RS-485 communications (0 to 127). Default
address is 0. RS-232 should have its own
(programmable) password.
Baud Rate
Allows communications Baud Rate to be set (2400
to 19.2K). Default is 9600.
Unit Alpha
Displays the first alphabetical character of the boiler
serial number [G (for “Gas-Fired”)]
Unit Year
Displays the year in which the boiler was
manufactured (00 – 99)
Unit Serial #
Displays the boiler numerical serial number (0000 –
9999). See the “Sample” serial # format below for a
boiler manufactured in 2011:
G-11-1234
C-More Year
Displays the year in which the C-More Control Box
was manufactured (00 – 99). The year is the first
two characters of the C-More serial number followed
by a space.
C-More Serial #
Displays the C-More Control Box serial number
(0000 – 9999) which appears after the year it was
manufactured.
C-More Alpha
Displays a single alphabetical character after the C-
More Serial # described above. See the “Sample”
serial # format below for a C-More manufactured in
2011:
11 1234 V
Software Version
Identifies the current software version of the control
box (Ver 0.0 to Ver 9.9).