Technical Documentation
Rev. 01
Power Factor Regulator
BLR-Q(U)
Page 36 of 39
Function
Factory setting
Range of setting
Customer setting
P-export alarm
disabled
disabled, M, DO, D, CP, O, F
Temp1 alarm
DO
disabled, M, DO, D, CP, O, F
Limit temperature 1
25°C
20°C – (temp2)
∆
T (temp. hysteresis) Temp1
1.0°C
0.5°C – 9.9°C
Temp2 alarm
M, D, O
disabled, M, DO, D, CP, O, F
Limit temperature 2
70°C
temp2 – 70°C
∆
T (temp. hysteresis) Temp2
1.0°C
0.5°C – 9.9°C
DI Input alarm
disabled
disabled, M, DO, D, CP, O, F
DI trigger
high
high / low
Frequency alarm
disabled
disabled, M, DO, D, CP, O, F
Limit low frequency
45.0Hz
45.0Hz – (limit high -0,1Hz)
Limit high frequency
65.0Hz
(limit low +0,1Hz) – 65.0Hz
Modbus baudrate
9600
1200 – 38400
Modbus parity
8E1
8E1, 8°1, 8N2
Modbus address
1
1 – 247
Storage interval (datalogger)
0 min
0 – 720 min
Synchronisation DI input
off
on / off
Setup DI input
High
High / low