Thermoglaze
TG-50 Parameter Settings
Tables 1, 2 and 3 below list of the temperature controller default settings and the Belshaw Factory
settings. When installing a new controller 3 of the default setting must be changed to the Belshaw
Factory settings.
•
Push and hold the scroll key
for 3 seconds, this will take you to the “
SEt
” menu.
•
Push the scroll key
once to access the “
LocK
” parameter.
•
Push the Up
or down
arrow keys to change “
LocK
” to “
nonE
”.
•
Push the scroll key
to page through the settings and the Up
or down
arrow keys to
change the settings listed in the Belshaw “
Factory
” column. (see tables 1, 2 and 3)
When finished setting parameters.
•
Continue pushing the scroll key
until you are back to “
LocK
”.
•
Push the Up
or down
arrow keys to set “
LocK
” to “
uSEr
”.
•
Push the reset key
to return normal operation.
Default Settings:
In the event that parameters have been modified without recording the modifications, change each
parameter to match those listed in Tables 1, 2 and 3 listed below (controller parameter default settings).
Then adjust
SP1H, PB,
OUT2
and the
LocK
parameters as listed in Belshaw “
Factory
” below. Then set
SP1
to 420ºF.