background image

Technical data sheet

SF24A-MP

www.belimo.com

SF24A-MP • en-gb • 2020-12-14 • Subject to change

1 / 7

Communicative rotary actuator fail-safe for 
adjusting dampers in technical building 
installations

• Air damper size up to approx. 4 m²
• Torque motor 20 Nm
• Nominal voltage AC/DC 24 V
• Control modulating, communicative 2...10 V

 

variable

• Position feedback 2...10 V variable
• Conversion of sensor signals
• Communication via Belimo MP-Bus

Technical data

Electrical data Nominal voltage

AC/DC 24 V

Nominal voltage frequency

50/60 Hz

Nominal voltage range

AC 19.2...28.8 V / DC 21.6...28.8 V

Power consumption in operation

8.5 W

Power consumption in rest position

3.5 W

Power consumption for wire sizing

11 VA

Connection supply / control

Cable 1 m, 4 x 0.75 mm²

Parallel operation

Yes (note the performance data)

Functional data Torque motor

20 Nm

Torque fail-safe

20 Nm

Communicative control

MP-Bus

Operating range Y

2...10 V

Input Impedance

100 kΩ

Operating range Y variable

Start point 0.5...30 V
End point 2.5...32 V

Options positioning signal

Open/close
3-point (AC only)
Modulating (DC 0...32 V)

Position feedback U

2...10 V

Position feedback U note

Max. 0.5 mA

Position feedback U variable

Start point 0.5...8 V
End point 2.5...10 V

Position accuracy

±5%

Direction of motion motor

selectable with switch L/R

Direction of motion variable

electronically reversible

Direction of motion fail-safe

selectable by mounting L/R

Manual override

by means of hand crank and locking switch

Angle of rotation

Max. 95°

Angle of rotation note

adjustable starting at 33% in 2.5% steps (with 
mechanical end stop)

Running time motor

150 s / 90°

Running time motor variable

70...220 s

Running time fail-safe

<20 s / 90°

Running time fail-safe note

<20 s @ -20...50°C / <60 s @ -30°C

Adaptation setting range

manual

Adaptation setting range variable

No action
Adaptation when switched on
Adaptation after using the hand crank

Override control

MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position, AC only) = 50%

Summary of Contents for SF24A-MP

Page 1: ...erating range Y 2 10 V Input Impedance 100 k Operating range Y variable Start point 0 5 30 V End point 2 5 32 V Options positioning signal Open close 3 point AC only Modulating DC 0 32 V Position feed...

Page 2: ...raft or in any other airborne means of transport Outdoor application only possible in case that no sea water snow ice insolation or aggressive gases interfere directly with the device and that it is e...

Page 3: ...gnal A range of settings can be adapted using the PC Tool see MFT P documentation Accessories Gateways Description Type Gateway MP zu BACnet MS TP UK24BAC Gateway MP to KNX UK24EIB Gateway MP to Modbu...

Page 4: ...s AC DC 24 V modulating Operation on the MP Bus Cable colours 1 black 2 red 3 white 5 orange Cable colours 1 black 2 red 3 white 5 orange Functions Functions when operated on MP Bus Connection on the...

Page 5: ...ly 0 100 with positioner SG Minimum limit with positioner SG Follow up control position dependent Control with 4 20 mA via external resistor Functional check Caution The operating range must be set to...

Page 6: ...ts Override control and limiting with AC 24 V with rotary switch 1 Caution This function is only guaranteed if the start point of the operating range is defined as min 0 5 V Control open close Control...

Page 7: ...7 Dimensions Dimensional drawings Clamping range Min 85 Min 15 Further documentation Overview MP Cooperation Partners Tool connections Introduction to MP Bus Technology Application notes For digital...