background image

Note: 

Perform settings on the auxiliary switch only in deenergised state.

1

Manual adjusting

Connect the actuator and move it into the desired position.

2

Auxiliary switch 1

Turn rotary knob until the arrow points to the vertical line.
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary 
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.

3

Auxiliary switch 2

Turn rotary knob until the arrow points to the vertical line. 
Turn the spindle clamp

2

 and consider the arrow direction of the auxiliary switch rotary knob at 

the same time.
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary 
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.
Release (or disengage) button 

1

.

4

Auxiliary switch - 2

Same procedure as for auxiliary switch 1 (step 

1

 to 

2

).

1

2

3

Note: 

Perform settings on the auxiliary switch only in deenergised state.

1

Manual override control

Turn the hand crank until the desired switching position is set.

2

Fasten the locking device

Turn the locking switch to the «Locked padlock» symbol.

3

Auxiliary switch 1

Turn rotary knob until the arrow points to the vertical line. 
The arrow direction always indicates the switching position (S1-S2 or S1-S3).
If the auxiliary switch should switch in the opposite direction, rotate the auxiliary switch rotary 
knob by 180°. Alternatively the switching position can be checked with a continuity tester
on the cable of the auxiliary switch.

4

Unlock the locking device

Turn the locking switch to the «Unlocked padlock» symbol or unlock with the hand crank.

5

Auxiliary switch  2

Same procedure as for auxiliary switch 1 (step 

1

 to 

4

).

3

5

1

4

2

S2A-F

Auxiliary switch unit, suitable for the spring return 

actuators NF..A.., SF..A.., LF..

Operating controls and indicators

www.belimo.com

S2A-F • en-gb • 2019-04-12 • subject to changes

3