W552

Indicates an action or condition that may cause 
irreversible damage to the actuator(s) or 
associated equipment.

Equipment damage!
Power consumption and input impedance 
must be observed. 

CAUTION

Indicates a potentially hazardous situation which, if 
not avoided, may result in minor or moderate injury. 
It may also be used to 
alert against unsafe practices.

Warnings and Cautions appear at appropriate 
sections throughout this manual. Read these carefully.

Hazard Identification

 G     Ground

 4     Power Supply Com

 5     Power Supply Hot

 6     Control Signal (-)

 7     Control Signal (+)

 8     Internal Use Only

 9     Internal Use Only

 10    Internal Use Only

  11     Feedback  (-)

  12      Feedback  (+)

Feedback (B)

 G     Ground

 4     Power Supply Com

 5     Power Supply Hot

 6     Control Signal (-)

 7     Control Signal (+)

 8     Internal Use Only

 9     Internal Use Only

 10    Internal Use Only

  11     Feedback  (-)

  12      Feedback  (+)

Feedback (A)

Control Signal

Actuator B

Actuator A

120 and 230 VAC

N L1

H L2

5

5

4

4

SY1 -110P (220P)

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.

                          3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY1 -110P (220P)

A

B

C

E

F

Contact Rating: 5A 125 VAC Max.

                          3A 250 VAC Max.

A-B (Open Indication)

LS4

LS3

A-E (Closed Indication)

SY Actuator Wiring Diagram, SY1…12-110P, (220P) – Multiple Wiring

NOTES SY1-110P (220P)

•  

Caution:

 Power supply voltage.

•  Do not change sensitivity or dip switch settings with 
    power applied.

Use of feedback is optional.

APPLICATION NOTES

5

4

Recommended twisted shielded pair for control wiring.  
Ground shielded wire at control panel chassis.  
Tape back ground at actuator.

Observe class 1 and class 2 wiring restrictions.

INSTALLATION NOTES

G

G

F6/F7... HS/HSU Butterfly Valves

SY Actuator Wiring Diagrams, SY1-110P (220P)

W552

Summary of Contents for F6 HS Series

Page 1: ...Installation and Maintenance Instructions for Belimo F6 F7 HS HSU Series Butterfly Valves March 2008 70103 00001D...

Page 2: ...lves should be stored in a weather protected area prior to installation Complete installation recommendations on page 38 Valve Size Cv Cv 10 Cv 20 Cv 30 Cv 40 Cv 50 Cv 60 Cv 70 Cv 80 Cv 90 F650HS U 2...

Page 3: ...Aircontrols USA Inc A B D C BHC 10 0 10 0 A B C D F6 Dimensional Data Dimensions in inches F7 Dimensional Data Dimensions in inches Ordering Information Please note that HS series BF valves over 18 a...

Page 4: ...22 00 8 50 8 10 UNCX1 75 50 50 F6150HSU 6 1058 2 19 9 00 22 50 9 50 8 10 UNCX2 00 50 Dimension A is compressed add 125 for relaxed state Maximum actuator ambient temperature is 122 F F6 HS Series Butt...

Page 5: ...t placement of valves and actuators on the assembly 4 Dimension D allows for actuator removal without the need to remove the valve from the pipe 5 Weather shields are available dimensional data upon r...

Page 6: ...06 3 7 15 27 44 70 105 115 F665HS U 2 196 0 10 6 12 25 45 75 119 178 196 F680HS U 3 302 0 20 9 18 39 70 116 183 275 302 F6100HS U 4 600 0 30 17 36 78 139 230 364 546 600 F6125HS U 5 1022 0 50 29 61 13...

Page 7: ...Specifications see actuator section for details Type industrial electric Supply Voltages 24 VAC 10 120 VAC 10 230 VAC 10 Control Scheme 2 Position Floating Point 2 10 VDC 0 10 VDC 4 20mA MFT Master Va...

Page 8: ...less Disc with Belimo SY Series Electric Actuation Maximum dimensions measured in inches MAX Close Off Valve Size GPM A B Max C Max D Max BHC Holes Lug Bolt Actuator Pressure psi F650HS 2 118 1 65 8 0...

Page 9: ...utterfly Valves Full rated Resilient Seat 304 Stainless Disc with Belimo SY Series Electric Actuation Maximum dimensions measured in inches MAX Close Off Valve Size GPM A B C D Max BHC Holes Lug Bolt...

Page 10: ...VAC factory set for 5 and 85 change of state Ambient Temperature 22 F to 150 F 30 C to 65 C Humidity Range up to 95 Housing Type IP67 NEMA 4 4X Housing Material die cast aluminum alloy Agency Listing...

Page 11: ...SY12 120 SR MFT 3500Nm 31150 in lbs 58s 70s 4 0A Hand Wheel 56kg 123 5 lb Electrical Connection conduit connector screw terminals Overload Protection thermally protected 135 C cut out Motor Protectio...

Page 12: ...SY12 230 SR MFT 3500Nm 31150 in lbs 58s 70s 2 2A Hand Wheel 56kg 123 5 lb Electrical Connection conduit connector screw terminals Overload Protection thermally protected 135 C cut out Motor Protectio...

Page 13: ...nches mm Inches mm Inches mm SY1 6 10 155 3 94 100 4 25 108 8mm 8mm SY2 3 10 04 255 7 48 190 7 87 200 12 99 330 7 87 200 SY4 6 12 40 315 8 86 225 9 21 234 14 96 380 11 81 300 SY7 8 16 54 420 8 86 225...

Page 14: ...see chart below Field adjustable if required Factory pre set and calibrated Do not adjust warranty voided LS2 Clockwise Decrease Closed Angle CLOSE Counter clockwise Increase Closed Angle LS1 Clockwi...

Page 15: ...TION NOTES WARNING CAUTION APPLICATION NOTES INSTALLATION NOTES CAUTION APPLICATION NOTES INSTALLATION NOTES WARNING CAUTION APPLICATION NOTES INSTALLATION NOTES WARNING WARNING CAUTION APPLICATION NO...

Page 16: ...L CLOSED Reverse Acting ON ON OFF ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON OFF ON 1 2 3 4 5 6 7 8 6 7 8 2 3 5 4 1 8 7 6 2 4 5 3 1 8 7 6 2 4 5 3 1 8 7 6 2 4 5 3 1 6 7 8 2 3 5 4 1 8 7 6 2 4...

Page 17: ...2488 1866 SY1 SY2 SY3 SY4 SY5 SY6 SY7 SY8 SY9 SY10 SY11 SY12 wire gauge 0 3A 0 5A 0 5A 0 6A 0 7A 0 8A 1 6A 2 0A 1 6A 2 0A 1 6A 2 2A 18 5051 3030 3030 2525 2165 1894 947 758 947 758 947 689 16 7937 47...

Page 18: ...Terminal 7 needs to be field wired to enable heater circuit 24 VAC Transformer Line Volts Open Close G Ground 1 Common 3 Open 4 Closed 5 Connect to 1 for fully open indication 6 Connect to 1 for full...

Page 19: ...ibited Terminals 4 and 6 need to be wired separately Do not change sensitivity or dip switch settings with power applied 24 VAC Transformer Line Volts G Ground 4 Power Supply Com 5 Power Supply Hot 6...

Page 20: ...n LS4 LS3 A E Closed Indication NOTES SY2 12 120SR MFT 230SR MFT Caution Power supply voltage SY Actuator Wiring Diagram SY1 5 24P and SY1 12 110P 220P Observe Class 1 and Class 2 wiring restrictions...

Page 21: ...1 Common 3 Open 4 Closed 5 6 7 HTR A B C D E F LS3 A C Open Indication LS4 D F Closed Indication Contact Rating 5A 250 VAC Max SY2 5 24 K1 Open Close K1 B K1 A Actuator A Actuator B G Ground 1 Common...

Page 22: ...6 Control Signal 7 Control Signal 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 11 Feedback 12 Feedback Feedback B G Ground 4 Power Supply Com 5 Power Supply Hot 6 Control Signal 7 Con...

Page 23: ...5 5 G PE G PE Actuator B Actuator A Address Adaption Y1 Y2 Address Adaption Y1 Y2 1 1 F6 F7 HS HSU Butterfly Valves SY Actuator Wiring Diagrams SY2 5 24SR MFT Multiple Wiring W552 SY Actuator Wiring...

Page 24: ...Supply Hot 6 Control Signal 7 Control Signal 8 Internal Use Only 9 Internal Use Only 10 Internal Use Only 11 Feedback 12 Feedback Feedback A Control Signal Actuator B Actuator A 120 and 230 VAC N L1 H...

Page 25: ...ed wire at control panel chassis Tape back ground at actuator Observe class 1 and class 2 wiring restrictions INSTALLATION NOTES Power Supply Com 120v N 230v L1 Power Supply Hot 120v H 230v L2 1 Y U5...

Page 26: ...may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirements without the need of an electrical ground connection Equipment damage Actuators may be connected in parallel Power consumption an...

Page 27: ...ve Electrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or o...

Page 28: ...ators with plenum rated cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA re...

Page 29: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Page 30: ...y also be used to alert against unsafe practices Warnings and Cautions appear at appropriate sections throughout this manual Read these carefully Hazard Identification INSTALLATION NOTES APPLICATION N...

Page 31: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Page 32: ...h plenum rated cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirement...

Page 33: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Page 34: ...ted cable do not have numbers on wires use color codes instead Actuators with appliance cables are numbered 3 Actuators may also be powered by 24 VDC 5 Meets cULus or UL and CSA requirements without t...

Page 35: ...lectrical Components During installation testing servicing and troubleshooting of this product it maybe necessary to work with live electrical components Have a qualified licensed electrician or other...

Page 36: ...to live electrical components could result in death or serious injury On Off 1 Neutral Blk 2 Hot Red Wht N Blk H Line Volts 2 5 120 VAC 230 VAC On Off On Off Control 24 VAC DC Power AF24 US AF24 S US...

Page 37: ...ied licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety precautions when exposed t...

Page 38: ...with piping ends TACK weld the flanges to the piping in several places Do NOT seam weld at this time Remove the lug bolts and carefully remove the valve body from the flanges Seam weld the entire fla...

Page 39: ...allation using welded flanges on page 30 of this document 8 Follow ASME flange alignment standards Section 335 1 1 Alignment a Piping Distortions Any distortion of piping to bring into alignment for j...

Page 40: ...to the fully closed position checking the actuator travel stop settings for proper disc alignment The valve should be operated to assure that no binding is taking place 6 The valve is now ready for op...

Page 41: ...Operator Manual or Automatic already attached to the valve shaft 4 Never remove the Operator from the valve while the valve is in the pipeline under pressure 5 Always be sure that the disc is cracked...

Page 42: ...42 70103 00001D 03 08 Subject to change Belimo Aircontrols USA Inc Notes Work Pad...

Page 43: ...lis MN 55426 4267 Phone 952 920 0131 With branches in MN RSD Total Control 26021 Atlantic Ocean Drive Lake Forest CA 92630 Phone 949 380 7878 With branches in CA NV OR AK AZ ID UT WA Saint Louis Boile...

Page 44: ...06810 Suite 101 Toll Free 800 543 9038 Sparks NV 89434 203 791 9915 Toll Free 800 987 9042 Fax 800 228 8283 775 857 4243 800 ACTUATE Fax 800 987 8875 203 791 9919 775 857 4255 South Customer Service...

Reviews: