background image

800-543-9038 

USA

866-805-7089 

CANADA

203-791-8396 

LATIN AMERICA / CARIBBEAN

40

Correct pointer mounting

position if actuator is at

full fail-safe.

Correct pointer mounting

position if actuator is at

5° preload.

Figure A

Installation Instructions

Mechanical Installation

  position the clamp so that the pointer section of the tab is pointing to 0° (see

Figure C) and the spline pattern of the clamp mates with spline of the actuator.
Slip the clamp over the spline.  (Use the same procedure if the “CW” side is out.) 
If your application requires a mechanical minimum position, read the

Rotation 

Limiting, Mechanical Minimum Damper Position

section.  

n

4.  Lock the clamp to the actuator using the retaining clip.
5. Verify that the damper is still in its full fail-safe position.
6.  Slide the actuator over the shaft.
7. Position the actuator in the desired location.
8.  Tighten the two nuts on the clamp using a 13mm wrench or socket using 11 ft-lb

of torque.

9.  Slip the stud of the anti rotation strap into the slot at the base of the actuator. 

The stud should be positioned approximately 1/16 of an inch from the closed end 
of the slot. Bend the strap as needed to reach the duct. Attach the strap to the
duct with #8 self tapping screws.

Short Shaft Installation

If the shaft extends at least 3/4” from the duct, follow these steps:
1.  Determine the best orientation for the universal clamp on the back of the

actuator. The best location would be where you have the easiest access to the V 
bolt nuts on the clamp.

2.  Engage the clamp to the actuator as close as possible to the determined location.
3.  Lock the clamp in place using the remaining retainer clip.
4.  Verify that the damper is still in its full fail-safe position.
5.  Slide the actuator over the shaft.
6.  Position the actuator in the desired location.
7.  Tighten the two nuts on the clamp using a 13mm wrench or socket using 11 ft-lb

of torque.

8.  Slip the stud of the anti-rotation strap into the slot at the base of the actuator. 

The stud should be positioned approximately 1/16 of an inch from the closed end 
of the slot. Bend the strap as needed to reach the duct. Attach the strap to the
duct with #8 self tapping screws.

9.  If damper position indication is required, use the optional IND-EFB pointer. See 

Figure A

.

Jackshaft Installation

The EFB, EFX… series actuator is designed for use with jackshafts up to 1.05” in 
diameter.  In most applications, the EFB, EFX actuator may be mounted in the same 
manner as a standard damper shaft application.  If more torque is required than one 
EFB, EFX actuator can provide, a second EFB, EFX actuator may be mounted to the
jackshaft. 

See wiring guide for wiring details.

EF ACTUATORS WHICH MAY BE USED ON ONE SHAFT
Model

Maximum Quantity

Per Shaft

Minimum Shaft

Diameter

EFB24(-S)(N4)

2*

3/4”

EFX24(-S)(N4)
EFB120(-S)(N4)
EFX120(-S)(N4)
EFB24-MFT(-S)(N4)

3**

3/4” for 2x

1” for 3x

EFX24-MFT(-S)(N4)
* Wired in parellel
** Wired master-slave

MOUNTING:  

If the actuators are mounted on the opposed ends of the shaft, the 

actuator direction must be selected carefully.  Usually, the direction of rotation is 
reversed.

Multiple Actuator Mounting

If more torque is required than one EFB, EFX actuator can provide, a second EFB, EFX
actuator may be mounted to the shaft.  

NOTE:

  The manual positioning mechanism cannot be used in multiple actuator

applications.

Special Wiring and Additional Information:  See wiring guide

 N40103 - 09/11 - Sub

ject to chan

g

e.

 © Belimo 

Aircontrols 

(USA

), Inc.

Summary of Contents for EFB Series

Page 1: ...Parallel blade No edge seals Default 2 to 10 VDC Default 150 seconds EFB and EFX Series Spring Return Direct Coupled Actuator A Applications Minimum 270 in lb Torque For damper areas up to 66 sq ft Fo...

Page 2: ...tion Do it easily with a simple switch modulating actuators Microprocessor controlled brushless DC motor increases actuator life span and reliability provides constant running time modulating actuator...

Page 3: ...X24 EFX24 S On Off Spring Return 24 V Technical Data EFB24 EFB24 S EFX24 EFX24 S Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 Power consumption running 9 5 W holding 4 5 W Transformer sizing 16 VA cla...

Page 4: ...ed and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and...

Page 5: ...Centered Field Selectable EF_NEMA4_dims EFB24 N4 EFB24 S N4 EFX24 S N4 H NEMA 4 On Off Spring Return 24 V Technical Data EFB24 N4 EFB24 S N4 EFX24 S N4 H Power supply 24 VAC 20 50 60 Hz 24 VDC 20 10 P...

Page 6: ...red under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Dam...

Page 7: ...1 05 Centered Field Selectable EF_NEMA2_dims Technical Data EFB120 EFB120 S EFX120 EFX120 S Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 10 Power consumption running 9 5 W holding 4 5 W VA rat...

Page 8: ...tors shall be cULus approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provid...

Page 9: ...8 3 K9 2 supplied 1 2 Field Selectable 3 4 Centered Default 1 05 Centered Field Selectable EF_NEMA4_dims Technical Data EFB120 S N4 EFX120 S N4 H Power supply 100 240 VAC 10 20 50 60 Hz 100 125 VDC 1...

Page 10: ...and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo EFB120 S N4 EFX120 S N4 Load L W066_EFB X 120_N4_11 On Off wiring Wht Blk EFB120...

Page 11: ...sions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 59 15 2 76 70 1 38 35 0 52 13 3 7 40 188 1 97 50 0 20 5 2 5 63 143 0 33 8 3 2 13 54 2 44 62 11 32 287 5 13 09 332 5 1...

Page 12: ...d under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damag...

Page 13: ...from full fail safe to provide automatic compression against damper gaskets for tight shut off Dimensions Inches mm 4 74 120 5 3 15 80 1 06 27 0 19 4 85 0 53 13 5 5 43 138 4 41 112 0 20 5 2 5 43 138 0...

Page 14: ...ernational Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and disconnect as required 2 CAUTION Equipment Damage Actuators may be c...

Page 15: ...onfiguration Default parameters for 2 to 10 VDC applications of the EFB24 MFT EFX24 MFT actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parame...

Page 16: ...Insulation so an electrical ground is not required to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control...

Page 17: ...H actuator are assigned during manufacturing If required custom versions of the actuator can be ordered The parameters noted in the Technical Data table are variable These parameters can be changed b...

Page 18: ...ed to meet agency listings Actuators shall be cULus Approved and have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by...

Page 19: ...ot on the correct side of the actuator mount it onto the correct side 3 Slide the actuator onto the shaft and tighten the nuts on the V bolt with a 13mm wrench to 11 ft lb of torque 4 Slide the anti r...

Page 20: ...03 791 8396 LATIN AMERICA CARIBBEAN 38 Installation Instructions K9 2 Universal Clamp 1 2 3 4 1 05 3 4 1 05 1 2 11 16 1 2 3 4 1 2 11 16 1 2 stainless steel 18 5 ft lb 11 ft lb 13mm N40103 09 11 Subjec...

Page 21: ...r example for fan start up The switching function at the fail safe position is fixed at 10 the other switch function is adjustable between 10 to 85 for NEMA 4 versions the second switch is fixed at 85...

Page 22: ...using the remaining retainer clip 4 Verify that the damper is still in its full fail safe position 5 Slide the actuator over the shaft 6 Position the actuator in the desired location 7 Tighten the tw...

Page 23: ...here a damper has a designed rotation less than 90 An example would be a 45 or 60 rotating damper The other application would be to set a minimum damper position which can be easily set or changed wit...

Page 24: ...tion Without Power The actuator damper installation may be tested without power at the actuator Refer to the manual positioning section of the instructions Move the damper to its full non fail safe po...

Page 25: ...pled mounting applications The KH EFB may also be used to simultaneously direct couple to a damper shaft and provide an additional crank arm connection to a second damper KH EFB For round shafts up to...

Page 26: ...ops the pulses to the motor when it senses a stall condition The DC motor remains energized and produces full rated torque to the load This helps ensure that dampers are fully closed and that edge and...

Page 27: ...following rules are followed 1 The transformers are properly sized 2 All No 1 wires from all actuators are tied together and tied to the negative leg of the control signal See wiring diagram Wire Leng...

Page 28: ...Signal position Actuator operates properly Step 7 Step 5 5 Check input signal with a digital volt meter DVM Make sure the input is within the range of the actuator NOTE The input signal must be above...

Reviews: