CRK24-B1

Functions

Chilled ceiling with dew point limiter

Digital input di2

If the optional connectable dew point limiter responds, then the output 

ao1 is overridden to 6 V by means of the input di2 (external dew point 

limiter). The 6-way ball valve moves into neutral position.

Typical applications

Chilled ceiling systems in which one dew point limit is required.

1 2

7

~

~

ao1

U5

1

4

di2

AC 24 V

CRK24-B1

1 2

5

U5

6

3

Y

Belimo actuator for 6-way valve

Cooling / Heating
Dew point reached

Dew point

  

[V] 

ao1 

10 

7.3 

4.7 

0  10 

33 

66

90  100  [%] 

ao1

(heating)

ao1

(cooling)

Dew point

External setpoint shift

Analogue input ai2

1  2 

0 … 10 V 

ai2 

AC 24 V 

CRK24-B1 

An external DC 0...10 V signal at the analogue input ai2 can be used to 

raise the basic setpoint by 0 ... 10 K (corresponding to  

0 … 10 V).

Typical application

Summer/Winter Compensation

W [°C]

S [V]

5.0

0

26

21

16

10

Notes

A negative shift is possible by setting the basic setpoint to the desired 

final setpoint, e.g. from 21°C (default value) to 16°C. This results in the 

following correspondences:

–  0 … 5 V: 16 … 21°C and

–  5 … 10 V: 21 … 26°C (see illustration at the left).

Legend

W Setpoint
S

Shift signal

Setpoint shift

Summary of Contents for CRK24-B1

Page 1: ...tion 10 Pre comfort 11 Energy hold off EHO 11 Chilled ceiling with dew point monitoring 12 External setpoint shift 12 External temperature sensor ai1 13 Analogue outputs 13 Dimensions installation com...

Page 2: ...imo eu Heated chilled ceiling applications Single room controller Accessories CRK24 B1 6 way ball valve and rotary actuators EXT K3B2 LR24A MP LR24A SR Diagnostic and setting device ZTH EU Setting for...

Page 3: ...LR24A MP LR24A SR actuator This controller should therefore only be utilised in the actuator in combination with the 6 way ball valve The multitude of override features makes possible an economically...

Page 4: ...4 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...

Page 5: ...2 10 V max 5 mA Norms and Standards Protection class III Safety extra low voltage Degree of protection IP30 EN 60529 Mode of operation Type 1 EN60730 1 Software class A EN 60730 1 EMC CE according to...

Page 6: ...t analogue input ai1 External setpoint shift An external DC 0 10 V signal at the analogue input ai2 can be used to shift the basic setpoint by 0 10 K e g for summer winter compensation The functions a...

Page 7: ...n be started with the mode switch which makes it possible to check the controller including nominal voltage AC 24V The three LEDs status display are used thereby to display the voltage level and the s...

Page 8: ...8 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...

Page 9: ...nt range 15 36 C Operation Mode selection switch AUTO ECO MAX Mode display LED AUTO ECO MAX Setpoint adjustment rotary knob 3 K Inputs Pre comfort Dew point limitation Energy hold off EHO External tem...

Page 10: ...int WA 1 K dead band 3 K Pre comfort Offset cooling Energy hold off fix 15 C building protection fix 40 C building protection Frost fix 10 C without function Setpoint calculation Examples Comfort Pre...

Page 11: ...gy Hold Off EHO Digital input di2 If a local detector e g a window switch has an effect on the digital input di2 and closes the corresponding contact then the room will be regulated in energy savings...

Page 12: ...r 6 way valve Cooling Heating Dew point reached Dew point l V ao1 10 7 3 4 7 2 0 10 33 66 90 100 ao1 heating ao1 cooling Dew point External setpoint shift Analogue input ai2 1 2 5 0 10 V ai2 AC 24 V C...

Page 13: ...e required The simultaneous utilisation of Pre comfort at di1 is possible although in this case a switchover to the internal sensor is made see also Pre comfort As a result the current room temperatur...

Page 14: ...14 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...

Page 15: ...housing to release the pcb 3 Remove the PCB Rotary knob for setpoint adjustment If the rotary knob has been removed proceed as follows a Insert the rotary knob approximately half way and turn it clock...

Page 16: ...oning 1 Assemble the baseplate of the housing and connect the cables see page 15 2 Configure the DIP switches on the printed circuit board according to the required application 3 Assemble the printed...

Page 17: ...d diameter and the transformer sizing Nominal voltage AC 24 V LED status indication Scenario A Scenario B Scenario C MAX red flash flash permanently on ECO orange flash flash permanently on AUTO green...

Page 18: ...18 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...

Page 19: ......

Page 20: ...73 info belimo de www belimo de At no charge Orders Tel 0711 1 67 83 83 Technical Consultation Tel 0711 1 67 83 84 Fax 0711 1 67 83 73 Personal consultation with Regional Sales Director in Berlin Hano...

Reviews: