Functions
Chilled ceiling with dew point limiter
Digital input di2
If the optional connectable dew point limiter responds, then the output
ao1 is overridden to 6 V by means of the input di2 (external dew point
limiter). The 6-way ball valve moves into neutral position.
Typical applications
Chilled ceiling systems in which one dew point limit is required.
1 2
7
~
~
ao1
U5
1
4
di2
AC 24 V
CRK24-B1
1 2
5
U5
6
3
Y
Belimo actuator for 6-way valve
Cooling / Heating
Dew point reached
Dew point
l
[V]
ao1
10
7.3
4.7
2
0 10
33
66
90 100 [%]
ao1
(heating)
ao1
(cooling)
Dew point
External setpoint shift
Analogue input ai2
1 2
5
0 … 10 V
ai2
AC 24 V
CRK24-B1
~
An external DC 0...10 V signal at the analogue input ai2 can be used to
raise the basic setpoint by 0 ... 10 K (corresponding to
0 … 10 V).
Typical application
Summer/Winter Compensation
W [°C]
S [V]
5.0
0
26
21
16
10
Notes
A negative shift is possible by setting the basic setpoint to the desired
final setpoint, e.g. from 21°C (default value) to 16°C. This results in the
following correspondences:
– 0 … 5 V: 16 … 21°C and
– 5 … 10 V: 21 … 26°C (see illustration at the left).
Legend
W Setpoint
S
Shift signal
Setpoint shift
Summary of Contents for CRK24-B1
Page 4: ...4 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...
Page 8: ...8 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...
Page 14: ...14 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...
Page 18: ...18 20 S4 CRK24 B1 en v1 2 06 2016 subject to changes www belimo eu CRK24 B1...
Page 19: ......