background image

Technical data sheet

AVK230A-3

Globe valve actuator with emergency 

control function for 2-way and 3-way 

globe valves

•  Actuating force 2000 N

•  Nominal voltage AC 230 V

•  Control 3-point

•  Nominal stroke 32 mm

•  Design life SuperCaps: 15 years

 

Technical data

Electrical data   Nominal voltage

AC 230 V

  Nominal voltage frequency

50/60 Hz

  Nominal voltage range

AC 85...265 V

  Power consumption in operation

3.5 W

  Power consumption in rest position

1.5 W

  Power consumption for wire sizing

6.5 VA

  Connection supply / control

Cable 1 m, 4 x 0.75 mm²

  Parallel operation

Yes (note the performance data)

Functional data   Actuating force motor

2000 N

  Setting emergency setting position (POP) Actuator spindle retracted / extended, 

adjustable (POP rotary button)

  Manual override

with push-button

  Nominal stroke

32 mm

  Actuating time motor

150 s / 32 mm

  Actuating time emergency control 

function

35 s / 32 mm

  Sound power level motor

60 dB(A)

  Sound power level emergency control 

position

60 dB(A)

  Position indication

Mechanically, 5...32 mm stroke

Safety   Protection class IEC/EN

II reinforced insulation

  Protection class UL

UL Class 2 Supply

  Degree of protection IEC/EN

IP54

  Degree of protection NEMA/UL

NEMA 2, UL Enclosure Type 2

  EMC

CE according to 2014/30/EU

  Low voltage directive

CE according to 2014/35/EU

  Certification IEC/EN

IEC/EN 60730-1 and IEC/EN 60730-2-14

  Certification UL

cULus according to UL 60730-1A, UL 60730-2-

14 and CAN/CSA E60730-1:02

  Mode of operation

Type 1.AA

  Rated impulse voltage supply / control

4 kV

  Control pollution degree

3

  Ambient temperature

0...50°C

  Non-operating temperature

-40...80°C

  Ambient humidity

95% r.h., non-condensing

  Maintenance

Maintenance-free

Weight   Weight

4.4 kg

Terms   Abbreviations

POP = Power off position / emergency setting 

position

CPO = Controlled power off / controlled 

emergency control function

PF = Power fail delay time / bridging time

Safety notes

!

•  This device has been designed for use in stationary heating, ventilation and air 

conditioning systems and must not be used outside the specified field of application, 

especially in aircraft or in any other airborne means of transport.

www.belimo.eu

AVK230A-3 • en-gb • 2017-03-09 • subject to changes