AFX24LON

Operating Controls and Indicators

1 Membrane key and green LED display

Off

No voltage supply or malfunction

On

Operation

Press button

Switches on angle of rotation adaption followed 
by standard operation

2 Membrane key and yellow LED display

Off

The actuator is integrated ready-for-operation in 
the LONWORKS® network.

On

No application software is loaded in the actuator.

Blinking
(flashing interval 2 seconds)

The actuator is ready-for-operation, but not 
integrated in the LONWORKS® network 
(unconfigured).

Other flashing codes

A fault is present in the actuator.

Press button

Service Pin Message will be sent to the 
LONWORKS® network.

3 Service plug 

For connecting MFT parameterizing and service tools

Operating Controls

The hand crank, interlocking switch and direction of rotation switch are provided 
on both sides.

1

2

3

Service

Adaption

 M40024 - 07/11 - Subject to change.