AFX24LON
Operating Controls and Indicators
1 Membrane key and green LED display
Off
No voltage supply or malfunction
On
Operation
Press button
Switches on angle of rotation adaption followed
by standard operation
2 Membrane key and yellow LED display
Off
The actuator is integrated ready-for-operation in
the LONWORKS® network.
On
No application software is loaded in the actuator.
Blinking
(flashing interval 2 seconds)
The actuator is ready-for-operation, but not
integrated in the LONWORKS® network
(unconfigured).
Other flashing codes
A fault is present in the actuator.
Press button
Service Pin Message will be sent to the
LONWORKS® network.
3 Service plug
For connecting MFT parameterizing and service tools
Operating Controls
The hand crank, interlocking switch and direction of rotation switch are provided
on both sides.
1
2
3
Service
Adaption