11.5 IO-Link Master Ports (X1 - X8,
Ch. A/C/Q/ Pin 4)
11 Technical data
11.5.1 Configured as a digital input
Input connection
Type 1 as per IEC 61131-2
Nominal input voltage
24 V DC
Input current
Typically 3 mA
Channel type
Normally open, p-switching
Number of digital inputs
8
Status indicator
Yellow LED
Diagnosis indicator
Red LED per channel
Table 51: IO-Link Master Ports configured as digital inputs
11.5.2 Configured as a digital output (except 0980 ESL
3x8-121)
Attention:
Power is supplied to the 500 mA outputs via the U
S
power
supply.
Output type
Normally open, p-switching
Nominal output current per channel
Signal status “1”
Signal status “0”
Min. (U
S
-1 V)
max. 2 V
Max. output current per device
16 A (M12 Power) (for U
L
application 9 A)
6 A (M12 Hybrid)
Short-circuit/overload protected
yes/yes
Behavior in case of short circuit or
overload
Disconnection with automatic power on
Number of digital outputs
LioN-P 30: max. 8 (Pin 4)
LioN-P 60: max. 8 (Pin 4) + 4 (Pin 2)
Status indicator
LED yellow per output
Diagnosis indicator
Red LED per channel
Table 52: IO-Link Master Ports configured as digital outputs
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
100