Technical data
60
10.4 Power supply for the actuators
Technical manual LioN-P EtherCAT® Digital-I/O
Release 1.0 11/2016
10.4
Power supply for the actuators
10.5
Inputs
10.6
Outputs
Nominal voltage U
L
24 V DC (SELV/PELV)
Voltage range
18-30 V DC
Electric isolation
Yes
Threshold value of the undervoltage detection Typ. 18 V
Delay time of the undervoltage detection
< 20 ms
Reverse polarity protection
Yes
Operational indicator (U
L
)
LED green, 18,6 V <= U
L
<= 30 V
LED red, U
L
< 18,6 V or U
L
> 30 V
Table 51: Information about the power supply for the actuators
Input connection
Type 3 as per IEC 61131-2
Nominal input voltage
24 V DC
Input current at 24 V DC
Typically 5 mA
Short-circuit protection
Yes
Channel type
Normally open, p-switching
Number of digital channels
16 with 16DI
0 with 16DO
8 with 8DI/8DO
Status indicator
LED yellow for channel A, LED white for
channel B
Diagnosis indicator
LED red for each slot
Port
M12 socket, 5-pin
See pin assignment
Table 52: Input information
Output connection
Typically 2 A as per IEC 61131-2
Nominal output current per channel:
Signal status “1”
Signal status “0”
2 A, see Info 1
max. 2 A
Max. 1 mA (according to specification)
Table 53: Output information