Diagnostic properties of the modules

48

7.7 Alarm and error messages of 

LioN-P/-R modules via PROFINET

Technical manual  LioN-P/ -R PROFINET

Release 1.2 02/2016

7.7

Alarm and error messages of LioN-P/-R 

modules via PROFINET

If both LioN-P/-R modules detect an error condition, an alarm message will 
be triggered. The modules support diagnostic alarms. Diagnostic alarms are 
triggered in case of peripheral faults such as overload, short-circuit, and 
undervoltage.

An alarm is triggered in case of an incoming event (such as sensor short-
circuit) as well as an outgoing event.

The evaluation of the alarms depends on the PROFINET I/O controller used.

7.7.1

Alarm evaluation in STEP 7

In 

STEP 7

 the user program execution is interrupted through the triggering of 

a diagnostic alarm, and a diagnostic block is called. The following blocks are 
used:

Initial information on the cause of the error and error type is already delivered 
based on the OB called and its start information. You can receive more 
detailed information about the error event in the error OB by calling SFB 54 
RALRM (read supplementary alarm information). For this, SFB 54 must be 
called in every error OB.

If the error OB called does not exist in the CPU, the CPU goes into the STOP 
operating state.

It is also possible to call a diagnostic data record using its data record number 
with the system function block SFB 52 “RDREC” in OB 1.

 Note

Alarm and error messages are only transmitted via PROFINET when the 
parameter for diagnostics is activated in the configuration of the modules in 
the control system.

Cause of the alarm

OB call

Peripheral error (short-circuit, overload, wire 
breakage, undervoltage of an I/O module)

OB B2

Complete failure of the system

OB B6

Summary of Contents for 934 692-001

Page 1: ...Technical support support automation belden com Technical manual LioN P PROFINET 0980 ESL 301 xxx 0980 ESL 303 xxx 0980 ESL 391 xxx 0980 ESL 393 xxx LioN R PROFINET 0980 ESL 801 PNET 16DI M12 R 0980 E...

Page 2: ...2 Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 3: ...Module variants 14 3 1 2 Accessories 15 4 Assembly and wiring 17 4 1 General information 17 4 2 Outer dimensions 19 4 2 1 Module 0980 ESL 803 19 4 2 2 Module 0980 ESL 303 111 20 4 2 3 Module 0980 ESL...

Page 4: ...01 xxx 0980 ESL 391 xxx 39 6 1 1 Input data 39 6 2 16DO modules 0980 ESL 802 PNET 16DO M12 R 0980 ESL 302 xxx 0980 ESL 392 xxx 39 6 2 1 Input data 39 6 2 2 Output data 40 6 3 8DI 8DO modules 0980 ESL...

Page 5: ...s 49 8 The integrated web server 51 8 1 The Home page 51 8 2 The Configuration page Config 52 8 3 The Status page 53 8 4 The Contact page 54 8 5 Reading the process and diagnostic data 55 9 Technical...

Page 6: ...Content 6 Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 7: ...used in this manual are used exclusively to explain how to operate and apply the LioN P and LioN R modules with PROFINET IO interface Please contact us if you have any detailed questions on installing...

Page 8: ...or substantial damage to property will occur if the required safety measures are not taken WARNING Means that death serious physical injury or substantial damage to property can occur if the required...

Page 9: ...2 02 2016 1 3 Version information 9 1 3 Version information Index Created Changed Changed Version number Version 1 0 Version 1 1 Version 1 2 Date May 2013 December 2015 February 2016 Name department K...

Page 10: ...About this manual 10 1 3 Version information Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 11: ...in the industrial sector The industrial environment is distinguished by the fact that the consumer is not connected directly to the public low voltage network Additional measures are required for use...

Page 12: ...re based on the requirement profiles described by ZVEI VDMA or equivalent organizations Only electricians who are familiar with the content of this manual are authorized to install and maintain the de...

Page 13: ...the modules allows a bus or star topology to be set up for the PROFINET I O network The implemented Media Redundancy Protocol MRP enables the design of a highly available network infrastructure The L...

Page 14: ...M12 Sturdy metal LioN R 16 DO LioN P 16 DO 0980 ESL 802 PNET 16DO M12 R SAP number 934 692 002 0980 ESL 302 111 singleprotocol SAP number 934 881 002 0980 ESL 302 121 singleprotocol SAP number 934 87...

Page 15: ...onnector socket straight 5 pin 0905 204 303 M Connection cable for power supply assembled on both sides with 7 8 connector straight 5 pin 0905 204 308 M Connection cable for power supply assembled on...

Page 16: ...straight 4 pin D coded 24AWG PVC with blue green casing flexible solid conductor unshielded 2 twisted wire pairs 0985 S4549 100 M Connection cable for PROFINET with M12 connector at both ends straight...

Page 17: ...ket and a distance of 196 8 to 198 3 mm for LioN P modules with M12 power L coded Note The modules have a ground connection with an M4 thread for the conduction of interference currents and the EMC im...

Page 18: ...es Note For UL application Only approved for interior use Please note the maximum elevation of 2000 meters Approved up to a maximum soiling level of 2 WARNING Terminals housings field wired terminal b...

Page 19: ...Assembly and wiring Technical manual LioN P R PROFINET Release 1 2 02 2016 4 2 Outer dimensions 19 4 2 Outer dimensions 4 2 1 Module 0980 ESL 803...

Page 20: ...Assembly and wiring 20 4 2 Outer dimensions Technical manual LioN P R PROFINET Release 1 2 02 2016 4 2 2 Module 0980 ESL 303 111...

Page 21: ...Assembly and wiring Technical manual LioN P R PROFINET Release 1 2 02 2016 4 2 Outer dimensions 21 4 2 3 Module 0980 ESL 303 121...

Page 22: ...ts M12 socket 4 pin D coded Color coding green Figure 1 Schematic drawing ports X01 X02 4 3 2 Connections for power supply with 7 8 5 pin Color coding gray Figure 2 Schematic drawing port X03 IN Port...

Page 23: ...le 0980 ESL 801 the two contacts 1 and 5 are not required for the power supply to the actuators However these two contacts are connected to each other on the connector and socket side to enable 5 pin...

Page 24: ...l Function 1 Vs 24V Sensor system power supply 2 GND_UL Ground reference potential Vaux 3 GND_VS Ground reference potential Vs 4 UL 24V Auxiliary supply electrically isolated PE 5 PE Functional ground...

Page 25: ...Color coding black Figure 6 Schematic drawing ports X1 to X8 Port Pin Function 16DI 16DO 8DI 8DO Sensor actuator 1 24 V DC n c 24 V DC ports X1 X4 n c ports X5 X8 2 IN B OUT B IN B ports X1 X4 OUT B p...

Page 26: ...Assembly and wiring 26 4 3 Port assignments Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 27: ...Service download_center index phtml On request the GSDML file is also sent by the support team The file for the LioN R PROFINET modules is named GSDML V2 3 LumbergAutomation 0980ESL80x yyyymmdd xml Th...

Page 28: ...ield devices I O Lumberg LioN R The LioN P PROFINET modules are available in the hardware catalog at PROFINET IO Other field devices I O Lumberg LioN P An EDS file is required for the configuration of...

Page 29: ...essed on PROFINET via a unique device name This can be freely assigned by the user but may only be used once on the network Select the module in HW Config and open the menu Edit Object properties In t...

Page 30: ...manual LioN P R PROFINET Release 1 2 02 2016 5 4 2 Assigning a device name to a LioN R module An online PROFINET connection between the programming device and the module is required to assign the dev...

Page 31: ...gured topology and the adjacent relationships determined by the I O devices The LioN P R PROFINET modules support the function of the device replacement without removable media PD The topology of the...

Page 32: ...the menu item Object properties Parameter In HW Config select the LioN R module In the configuration table right click the Slot 0 line and the PROFINET name of the module The following figure shows t...

Page 33: ...of modules 16DI 16DO 8DI 8DO The Fail Safe parameter This parameter is provided by the module types with digital outputs 16DO 8DI DO The firmware of the modules provides a fail safe function for the o...

Page 34: ...output channel The delay time begins after the status of the output channel changes i e when this is activated after a rising edge or deactivated after a falling edge After this time has elapsed the m...

Page 35: ...eset to the factory settings by clicking the Reset to factory settings button 5 5 Media Redundancy Protocol MRP Redundant PROFINET communication can be implemented with the LioN P modules via a ring t...

Page 36: ...s permissible The response monitoring time of all devices must be greater than the reconfiguration time typically 200 ms min 90 ms for LioN P modules It is recommended to use automatic network setting...

Page 37: ...Configuration and startup Technical manual LioN P R PROFINET Release 1 2 02 2016 5 5 Media Redundancy Protocol MRP 37 Example of setting up the response monitoring times in STEP7...

Page 38: ...Configuration and startup 38 5 5 Media Redundancy Protocol MRP Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 39: ...two bytes of status information of the digital inputs The bit assignment is as follows The following applies here 1A 8A Actual status of input channel A contact pin 4 of the M12 socket connections 1 t...

Page 40: ...hannel A contact pin 4 of the M12 socket connections 1 to 8 1B 8B Target status of output channel B contact pin 2 of the M12 socket connections 1 to 8 6 3 8DI 8DO modules 0980 ESL 803 PNET 8DI 8DO M12...

Page 41: ...tatus of output channel A contact pin 4 of the M12 socket connections 5 to 8 5B 5B Actual status of output channel B contact pin 2 of the M12 socket connections 5 to 8 6 3 2 Output data This module re...

Page 42: ...Assignment of the process data 42 6 3 8DI 8DO modules 0980 ESL 803 PNET 8DI 8DO M12 R 0980 Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 43: ...onfiguration of the module The value of this parameter can range from 0 to 255 ms the factory setting is 80 ms Target value Actual value Comment Active Active OK no diagnosis Off Off OK no diagnosis A...

Page 44: ...ase of a sensor short circuit a voltage error is reported Both channel indicators of the M12 input socket light up red and the relevant error bit for the sensor short circuit is set in the diagnosis b...

Page 45: ...the connections for the power supply of the actuators is monitored globally and on the module level If the actuator power supply UL goes outside the voltage range of 18 to 30 V an error is reported T...

Page 46: ...effect on the outputs and is not filtered but is reported immediately 7 6 Diagnostic display in the integrated web server The LioN R modules indicate the fault diagnosis on the status page of the inte...

Page 47: ...7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte 1 0 0 0 0 0 SC 0 LV US Byte 2 X8 X7 X6 X5 X4 X3 X2 X1 Table 14 Bit assignment for the 16 DI modules Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byt...

Page 48: ...agnostic alarm and a diagnostic block is called The following blocks are used Initial information on the cause of the error and error type is already delivered based on the OB called and its start inf...

Page 49: ...hannelProperties and ChannelErrorType for each error in the diagnostics data record The following figures illustrate this relationship based on the online diagnostics in Step7 To display the diagnosti...

Page 50: ...r messages of LioN P R modules via PROFINET Technical manual LioN P R PROFINET Release 1 2 02 2016 Confirming the Hexadecimal representation button in the window above opens a view of the diagnostic d...

Page 51: ...IP address In accordance with the PROFINET standard all PROFINET I O devices are delivered with the IP address 0 0 0 0 Consequently the modules must be assigned a free IP address that differs from th...

Page 52: ...se 1 2 02 2016 8 2 The Configuration page Config If you select the Config menu item from the menu bar of the Home window a new window with the configuration options will open On this page you can rese...

Page 53: ...of the two Ethernet ports of the modules in regard to connection transmission rate and transmission mode In the General Information area you will find the following system related information on the...

Page 54: ...he Contact page Technical manual LioN P R PROFINET Release 1 2 02 2016 8 4 The Contact page The address of the contact page is http IP Adresse contact htm This page provides information on the contact...

Page 55: ...ver The web server provides the data in standardized JSON format The data is accessed via the website The relevant address is http IP Adresse data jsn In higher programming languages the process and d...

Page 56: ...ng the process and diagno stic data Technical manual LioN P R PROFINET Release 1 2 02 2016 The response has the following object structure Process data Produced inputs Array a b Consumed outputs Array...

Page 57: ...80 RH Weight 615 g LioN R 480 g LioN P Housing material Die cast zinc Vibration resistance oscillation 15 g 5 500 Hz Shock resistance 50 g 11 ms Torques M6 M4 fixing screws M12 connector 1 0 Nm 0 5 N...

Page 58: ...range 18 30 V DC Power consumption of module electronics Typically 100 mA 0980 ESL 8xx Typically 120 mA 0980 ESL 3xx Typically 200 mA 0980 ESL 109 0980 ESL 309 Voltage level of the sensor power suppl...

Page 59: ...est Warning In case of polarity reversal a power supply unit with current regulation or an incorrect fuse will lead to destruction of the module Input connection Type 3 as per IEC 61131 2 Nominal inpu...

Page 60: ...per UL approval 9 A 12 A see info 2 0980 ESL 3xx As per UL approval 9 A 16 A per supply point Overload protection Yes Number of digital channels 0 with 16 DI 16 with 16DO 8 with 8DI 8DO Channel type N...

Page 61: ...it Off Not connected status Off no error X1 X8 B White Channel status B On Red Periphery error actuator overload short circuit Off Not connected status Off no error P1 Lnk Act P2 Lnk Act Green Etherne...

Page 62: ...Technical data 62 9 7 LEDs Technical manual LioN P R PROFINET Release 1 2 02 2016...

Page 63: ...Declaration of conformity Technical manual LioN P R PROFINET Release 1 2 02 2016 63 10 Declaration of conformity...

Page 64: ...Declaration of conformity 64 Technical manual LioN P R PROFINET Release 1 2 02 2016...

Reviews: