INSTALLATION INSTRUCTION

 

 

 

 

[email protected] 

 

 

 

 

USER INSTRUCTIONS 

1) DESCRIPTION 

DIN rail mountable primary switched-mode power supply with 187 - 550 VAC (250 - 725 VDC) input, suitable for single, two or three phase mains line and  
DC line. 

2) INSTALLATION 

Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point 
where the device is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see 
Fig.3).  
The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping. 
The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the 
ventilation or reduce the load (see Fig.8) 

3) CONNECTIONS 

The device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off 
input power and waited for internal capacitors discharge (minimum 1 minute) 
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of: 
60°C for ambient up to 45°C 
75°C for ambient up to 60°C 
90°C for ambient up to 70°C 
Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5) 

4) INPUT PROTECTION 

The device input is provided with varistors against overvoltage. Input isn’t provided with internal fuses; thus an external short circuit/overcurrent protection 
must be provided by the end user (see Fig.6). 
For operation on a single-phase or 2 phases system, a protection fuse on each phases must be provided. 
Surge protection: it is strongly recommended to provide external surge arresters (SPD) according to local regulations. 

5) AC INPUT CONNECTION 

The device can be connected to single phase AC line with rated Vin 230 VAC or two or three phase line with rated Vin 200 – 500 VAC (see Fig.7). Please 
connect first the PE. 

6) DC INPUT CONNECTION 

Connect L/L1 terminal to (+) positive pole, N/L2 terminal to (-) negative pole, L3 do not connected, and  

terminal to GND. Rated voltage 250 – 725 VDC. 

The device is also suitable for photovoltaic or wind turbine applications (see Fig.7). For UL applications use up to 500 VDC. 

7) OUTPUT CONNECTION 

The device is suitable for SELV and PELV circuitry.

 

Pay attention LDW240-72P is not SELV. 

Vout can be adjusted with a potentiometer to a wide range (see Fig.1) 
Check Vout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed 
the nominal power. 

8) PARALLEL CONNECTION AND REDUNDANCY 

Power supplies can be connected in parallel to increase power. 
Vout must be set uniformly (±100 mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution. 
Models with “P” suffix have an integrated ORing circuit. 
For redundant connection, use the Models “P” or an external isolating device must be used (see accessory device). 

9) OUTPUT PROTECTION 

The device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT). 
OL and SC:
 are controlled by a hiccup mode auto-reset protection with the following behaviour. 
OL behaviour:
 Max. OL = In x 1.5 with constant output voltage for max 5s. If the current is 

 In x 1.5 the unit enters the OL protection and starts an 

ON/OFF cycle (hiccup mode). 
SC behaviour: the device supplies the indicated short circuit peak current for 250 ms if the output current exceeds In x 1.5 the device enters into a 
controlled ON/OFF cycles (hiccup mode). The output voltage drops to a voltage value depending on the impedance of the failed load circuit. 
Output OV circuit protection: the output is protected against potential OV due to internal malfunction or coming from the load for  
Vout  

 Vnom x 1.2 – 1.3, depending on the model.  

OT protection: turns off the device if the internal temperature exceeds a safe limit. 
The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase 
cooling or reduce load (see Fig.8). 

10) FEEDING DC MOTORS 

It is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can 
trigger overcurrent protection (see accessory device). 
NOTE: motors can generate high conducted noise on the DC line. Therefore, it is not recommended to feed on the same line motors and equipment 
sensitive to noise. 

11) OPERATION WITH BATTERY 

When a battery is connected in parallel to the Output for backup purposes (see accessory device). 

 

Summary of Contents for LDW240 Series

Page 1: ...ficare il prodotto se durante il funzionamento si verificano guasti o anomalie inviarlo al produttore per il controllo Bel Power Solutions non si assume nessuna responsabilità per qualunque conseguenza derivante dall uso di questo materiale Lisez ces instructions avant l installation conservez ce manuel pour référence future Défaut de se conformer à ces instructions peut affecter les caractéristiq...

Page 2: ...evice is also suitable for photovoltaic or wind turbine applications see Fig 7 For UL applications use up to 500 VDC 7 OUTPUT CONNECTION The device is suitable for SELV and PELV circuitry Pay attention LDW240 72P is not SELV Vout can be adjusted with a potentiometer to a wide range see Fig 1 Check Vout before connecting the power supply to the load With output voltage set to the max value the cont...

Page 3: ...ne L Positive DC N Negative DC L3 do not connect earth ground Dimension W D H mm inc 54 2 12 110 4 33 115 4 52 Distance A B mm inc 20 0 8 50 2 0 Output Positive DC Negative DC Dry contact NC FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper d...

Page 4: ...al regulations FIG 7 INPUT CONNECTIONS AC LINE SINGLE PHASE AC LINE TWO PHASES AC LINE THREE PHASES DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 50 C 4 2 W C over 50 C NOTES Data may change without prior notice in order to improve the product Please refer to the latest version of the Installation Instruction for each product by vi...

Reviews: