BEL LDD960-UU Installation Instruction Download Page 5

5

 

INSTALLATION INSTRUCTION 

 

 

Asia-Pacific 

+86 755 298 85888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2020 Bel Power Solutions & Protection

 

BCM.00546_AC

 

 

LOGS

 

 

1.

 

Time

: time at which the log occurred. 

2.

 

Date

: date at which the log occurred. 

3.

 

Name

: unique log name 

4.

 

Primary value

: optional. 

5.

 

Secondary value

: optional. 

Every event is logged in the device FLASH memory. From the log menu the user can view their history. Use the UP/DOWN KEYS to navigate between logs, 2 
logs are visible simultaneously on the LCD. Logs are of 3 different kinds: 

info

alarms

 and 

events

. All 

info

 and 

alarms

 have an associated Modbus field with 

the current status (0 if inactive or 1 if active). For 

info

 and 

alarms

 a log is generated at each status transaction. In case of active alarm the front LED and the 

buzzer turn ON. 

 

ALARMS 

TYPE 

LCD NAME 

DESCRIPTION 

Battery disconnected 

Bat. discon. 

Active when no battery is detected by LDD960-UU. 

Battery Ri too high 

Bat Ri too high 

Active when measured battery internal resistance exceed the alarm threshold 

Battery under temperature 

Bat under temp. 

Active when the battery measured temperature (using the optional external sensor) is under the 

threshold specified in “

Battery min. temperature

” field. If active the battery charged is disabled.

 

Battery over temperature 

Bat over temp. 

Active when the battery measured temperature (using the optional external sensor) exceed the 

threshold specified in “

Battery max. temperature

” field. If active the battery charged is disabled.

 

Battery lifetime elapsed 

Bat lifetime 

Active when the actual calculated battery 

lifetime exceeds the threshold specified in “

Battery 

lifetime

” field.

 

Battery charge failure 

Bat charge fail 

Active when LDD960-UU could not charge the battery correctly. When active, the battery charger is 
disabled. Disconnect the battery to reset the alarm. 

Battery SoC < 25% 

Bat SoC 25% 

Active when the battery State of Charge is under 25% of the nominal full charge capacity. 

Battery over discharge current 

Bat over dis. I 

Active when the measured battery discharge current reaches the threshold specified in “

Battery 

max. discharge current” 

field. 

Battery low 

Bat low 

Active when the measured battery voltage is 

under the threshold specified in “

Battery low voltage

” 

field. 

Battery deep discharged 

Bat deep disch. 

Active when the battery measured voltage is under the threshold specified in “Battery deep discharge 
voltage” field.

 

Backup 

Backup 

Active when the system is in backup. 

Input under voltage 

In under volt. 

Active when the measured input voltage is under 90% of the “

Nominal output voltage

” field.

 

Input over voltage 

In over volt. 

Active when the measured input voltage exceeds 120% of the “

Nominal output voltage

” field.

 

Output under voltage 

Out under volt. 

Active when the measured output voltage is under 90% of the “

Nominal output voltage

” field.

 

Output over voltage 

Out over volt. 

Active when the measured output voltage exceeds 120% of the “

Nominal output voltage

” field.

 

Output overload 

Out overload 

Active when the measured output current reaches the threshold specified in “

Max. output current

” 

field. 

Input over current 

In over cur. 

Active when the measured input current reaches the 

threshold specified in “

Max. input current

” field.

 

Auxiliary output overload 

Aux overload 

 Active when an excessive load is detected on the auxiliary output. 

External temperature sensor error 

Ext. T error 

Active when the external temperature sensor is not connected while it’s use is mandatory like in 

NiMh battery charging. 

Backup time left < 25% 

Bkp left 25% 

Active when the system is in backup and the maximal backup time is less than the “

Max. backup 

time

” filed.

 

Warning over temperature 

Warn. over T 

Active when the internal temperature is high. If the temperature increases more the device may 
switch OFF. 

Error over temperature 

Error over T 

Active when the internal temperature is too high. To prevent damage the device switches OFF. 

 
 
 
 
 
 
 
 

Summary of Contents for LDD960-UU

Page 1: ...y out work on live parts Danger of fatal injury The product s enclosure may be hot allow time for cooling product before touching it Do not allow liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN...

Page 2: ... connected to the load to be backed up 10 Battery connection 2 poles are provided for battery connection This must be connected to the battery Please respect the correct polarity 11 Display area provides information regarding the device status 12 Control keys 4 push buttons are provided to navigate through the menus and to select the various functions USER INTERFACE SYMBOL NAME FUNCTION MENU KEY S...

Page 3: ...ckup the internal Coulomb counter is used to give an estimate of the residual charge of the battery Backup starts when the output voltage is lower than 90 of the Nominal output voltage Battery charger The battery charger supports various chemistries such Lead Acid Nickel Lithium and Super capacitors Other charging algorithms can be implemented by request contact factory The battery charger automat...

Page 4: ...ltaneously the buttons until you see the welcome message on the screen On the status screen the Cold start text is written beside the input icon Release the buttons PC shutdown and automatic restart PC shutdown In case the LDD960 UU is used to supply a PC it is possible to automatically shut down the PC after an adjustable time of backup For this the PC must run the POWERMASTER application provide...

Page 5: ...y SoC 25 Bat SoC 25 Active when the battery State of Charge is under 25 of the nominal full charge capacity Battery over discharge current Bat over dis I Active when the measured battery discharge current reaches the threshold specified in Battery max discharge current field Battery low Bat low Active when the measured battery voltage is under the threshold specified in Battery low voltage field B...

Page 6: ...wer side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the unit over the top edge of the rail 3 Slide it downward until it hits the stop 4 Press against the bottom for locking 1 2 3 4 DISMOUNTING 1 Pull down the slide clamp lever 2 Tilt the unit upward 3 ...

Reviews: