Installation and operating manual
EN
56 METPOINT
®
BDL compact
11.2.2.8.
Configuring analog sensors
Only possible with METPOINT
®
BDL compact models with fully equipped analog board.
Overview of the possible
Type
settings, including examples.
For
BEKO-Digital
see chapter 11.2.2.8.1 Selecting sensor type (example: BEKO Digital sensor) and chapter 11.2.2.1 BEKO
Digital dew point sensor
The
Alarm
and
Record
buttons, the
Resolution
for digital places as well as the
Short name
and the
Value name
are described
in chapter 11.2.2 Sensor settings.
For the labelling of the text fields, see chapter
Labelling and configuring text fields!
11.2.2.8.1. Type 0/4 – 20 mA / Type 0 – 1/10/30 V
Home
Settings
Sensor-settings
B1
Type
4 - 20 mA
For details regarding the scaling of the sensor (here:
type 4 – 20 mA
, corresponding to 0 – 25 bar), refer
to the data sheet of the sensor.
e.g. SP21
Home
Settings
Sensor settings
B1
right arrow (2. page)
In
Scal. 4 mA
, enter the lower scale limit. In
Scal. 20 mA
, enter the upper scale limit.
The
Ext. sensor supply voltage
is switched on when
the sensor requires it.
Press the
Set value to (offset)
button to set the
measured data from the sensor to a certain value
(offset).
The positive or negative difference of the
Offset
is
displayed.
Press the
Reset
button, to reset the
Offset
to zero.