25 / 124 EN
Multi Split Type Air Conditioner / User Manual
5 Installation
5�3 Specifications
Number of
units that
can be used
together
Connected
units
1-5 units
Compressor
stop/start
frequency
Stop time
3 min or more
Power source
voltage
voltage
fluctuation
within ±10% of
rated voltage
voltage drop
during start
within ±15% of
rated voltage
interval
unbalance
within ±3% of
rated voltage
1 drive 2 1 drive 3 1 drive 4 1 drive 5
Max. length for all
rooms
40/131 60/197 80/262 80/262
Max. length for
one indoor unit
25/82
30/98
35/115 35/115
Max. height
different between
indoor and
outdoor unit
15/49
15/49
15/49
15/49
Max. height
different between
indoor units
10/33
10/33
10/33
10/33
C
For the units adopt quick
connectors, no more than two
pipes can be connected, and the
Max.
length for each pipe is
7.5 meters.
When installing multiple indoor units with a
single outdoor unit, ensure that the length of the
refrigerant pipe and the drop height between the
indoor and outdoor units meet the requirements
illustrated in the following diagram:
C
The installation must be
performed in accordance
with the requirement of local
and national standards. The
installation may be slightly
different in different areas.