3.2. Installation
The diagrams below show examples of BEKOMAT
®
8/9 installation options.
NOTICE
Installation instructions
• Install a separate BEKOMAT
®
at each point where condensate might be produced.
•
Do not use cone-shaped fittings.
• Keep the pipes as short as possible.
•
Do not install filters/dirt traps in the condensate inlet.
• Only install ball valves in the condensate inlet line.
• The venting line must be installed above the highest possible condensate level.
• Observe the minimum installation heights.
Installation of BEKOMAT
®
8/9
Venting line A:
Lines ≥ ¾" must be equipped with ball valve
Condensate inlet B:
Pipes ≥ 2" (DN 50) must be installed with flange and ball
valve:
•
short inlet pipe!
•
Condensate inlet slope >1%!
•
No filter in condensate inlet!
Condensate discharge C:
Install pipe ≥1"
(for BEKOMAT
®
9: ≥ 2"):
•
Do not feed to a manifold!
•
Max. incline 5 m!
•
If the pipe is installed at an incline, the minimum
operating pressure is increased by 0.1 bar per metre!
For maintenance:
Manual drain D:
•
Lines ≥ ¾" must be equipped with ball valve
Bypass line E:
•
Lines ≥ 1" must be equipped with ball valve
B
A
C
D
E
Summary of Contents for BEKOMAT 8
Page 1: ...BEKOMAT 8 BEKOMAT 9 EN English 01 3048 Condensate drain Installation and operating manual ...
Page 2: ...Installation and operating manual EN 2 BEKOMAT 8 9 ...
Page 24: ...Installation and operating manual EN 24 BEKOMAT 8 9 8 Declaration of Conformity ...
Page 26: ...Installation and operating manual EN 26 BEKOMAT 8 9 ...
Page 27: ...EN Installation and operating manual BEKOMAT 8 9 27 ...