background image

3

1.  DESCRIPTION

The BA688CF Fieldbus Display is a panel
mounting instrument that can display up to eight
fieldbus process variables, together with their
units of measurement and tag information.  The
instruments are bus powered so no additional
power supply is required.

Two versions are available, one for Profibus PA
and the other for Fieldbus Foundation systems.
The Foundation Fieldbus version may be
ordered, or configured on-site, with alternative
function blocks allowing use with most Fieldbus
Foundation hosts.

      Order      Communication            Function
      Code            Protocol                    Blocks

BA688CF-P   Profibus PA

Eight Analogue Outputs
(8 x AO)

BA688CF-F

Fieldbus Revision 

1

Foundation

One Multiple Analogue

      

Output
(1 x MAO)

                  or Revision 2

Two Input Selectors
(2 x IS)

                       

The required Device Description files, which may
be downloaded from the Fieldbus Foundation or
BEKA web sites, depend upon which BA688CF-F
revision is selected.

The instrument’s communications protocol is
shown on the instrument information label, which
is located on the top outer surface of the
enclosure.

Nine selectable standard display formats enable
one, two, three or four process variables, some
with bargraphs to be displayed on one screen.
Alternatively, custom display formats including
text and simple graphics may be generated and
saved in permanent memory.

The six front panel push buttons that control the
instrument display may also be used for returning
operator acknowledgements, thus enabling the
Fieldbus Display to function as a simple operator
interface.    If larger industrial push buttons are
required for entering these acknowledgements,
up to six external switches may be connected to
the BA688CF.   These switch inputs may also be
used for returning the status of plant contacts.

The Fieldbus Display can be supplied with six
optional alarm outputs that may be linked to any
of the displayed fieldbus variables.

Housed in a robust 72 x 144 panel mounting DIN
enclosure, the BA688CF Fieldbus Display has an
IP66 front panel and is supplied with a gasket to
seal the joint between the instrument and the
panel.

1.1 Documentation

This instruction manual describes system design,
conditioning and installation of the BA688CF
fieldbus display.   For detailed programming
information please refer to the following guides
that can be downloaded from the BEKA website
www.beka.co.uk

Foundation Fieldbus Display – Fieldbus Interface

      Guide

Profibus Display – Fieldbus Interface Guide 

Fieldbus Display – Programming Guide

1.2  Version 2.0 firmware

This manual describes the enhanced features of
BA688CF fieldbus displays employing version 2.0
firmware that was released in December 2005.
Namely:

Standard screens increased from 4 to 9

Multiple bargraph limits added

Input scaling added

Fieldbus Foundation version now has
choice of fieldbus function blocks:

Revision 1  1 x MAO  (multiple
analogue output)

Revision 2   2 x IS (Input selector)

Selection can be made on-site.

The instrument’s firmware version can be
established using the ‘Unit Info’ function in the
main configuration menu – see section 5.3.9 of
this manual.

BA688CF displays employing version 2.0
firmware are backwards compatible with all
earlier versions of the instrument.

Summary of Contents for BA688CF

Page 1: ...Issue 6 8th May 2006 BA688CF Panel mounting Fieldbus Display Issue 6...

Page 2: ...rm Activation 5 3 5 3 Alarm Output 5 3 6 Display 5 3 6 1 Settings 5 3 6 2 Quick Access 5 3 6 3 Access Code 5 3 7 Keys 5 3 8 Code 5 3 9 Unit Info 5 3 10 Defaults 5 3 10 1 Display Defaults 5 3 10 2 Inte...

Page 3: ...simple operator interface If larger industrial push buttons are required for entering these acknowledgements up to six external switches may be connected to the BA688CF These switch inputs may also b...

Page 4: ...Profibus web sites or from the BEKA associates web site at ww beka co uk Fig 1 Simplified block diagram of BA688CF 2 1 Controls The user can scroll through the display screens by operating the Up or...

Page 5: ...her electrical circuits For reliable operation it is recommended that the cable connecting the Fieldbus Display to external switches is less than 5m long 3 2 Alarm outputs Each alarm output is a galva...

Page 6: ...he instrument secured with four panel mounting clips The BA688CF liquid crystal display has maximum contrast when viewed from directly ahead and slightly below the centre line of the instrument Fig 4...

Page 7: ...omplies with the requirements of the European EMC Directive 89 336 EEC For specified immunity all wiring should be in screened twisted pairs To prevent circulating currents cable screens should only b...

Page 8: ...ing the Up or Down button set the first digit of the code which will be flashing Pressing P will transfer control to the next digit which should be adjusted in the same way When all four digits have b...

Page 9: ...argraphs 5 3 2 Input Settings Only included in Profibus PA and Fieldbus Foundation Revision 1 instruments Omitted from Fieldbus Foundation Revision 2 instruments because these parameter can be easily...

Page 10: ...en alphanumeric characters This menu allows these tags to be entered After selecting the required variable the tag legend is entered character by character using the Up and Down push buttons Numbers u...

Page 11: ...enu see 5 3 5 1 5 3 6 Display 5 3 6 1 Settings The backlight brilliance and display contrast are adjustable from this sub menu 5 3 6 2 Quick Access This sub menu enables the Quick Access Menu which is...

Page 12: ...that the fieldbus function blocks selected are supported by the system host To change the BA688CF F revision highlight the required revision in the Restore Defaults menu and follow the screen prompts...

Page 13: ...13...

Page 14: ...plying variable Displayed variable is flashing Associated alarm has been activated Setpoints Bargraph on standard display format is shown dotted Displayed fieldbus variable is outside bargraph limits...

Page 15: ...ult this guide if one of the nine standard display screens is being used The guide may be requested from the BEKA sales office or downloaded from the BEKA web site at www beka co uk 8 3 Fieldbus Inter...

Page 16: ...ult finding During commissioning 7 1 After commissioning 7 2 Fieldbus Foundation 1 2 Display Programming Guide 8 3 Interface Guides 8 4 Revisions 1 2 5 3 10 3 Guarantee 7 5 Input scaling 5 3 2 Install...

Reviews: