10.3.9 Alarm delay:
dELA
This function enables activation of the alarm output
to be delayed for a fixed time following the alarm
condition occurring. The delay can be set in 1
second increments up to 3600 seconds. If a delay is
not required zero should be entered.
To adjust the delay select
dELA
using the
&
or
*
push button in the selected alarm sub-menu and
press
(
which will reveal the existing delay time in
seconds with one digit flashing. The required delay
time can be entered using the
&
or
*
push button
to adjust the flashing digit and the
(
button to
transfer control to the next digit. When set as
required press
)
to enter the value and return to
the
dELA
prompt in the alarm sub-menu.
The alarm annunciator will start flashing immediately
an alarm condition occurs and will continue for the
delay time, after which the alarm output will be
activated and the alarm annunciator will be
permanently activated.
10.3.10 Alarm silence time:
5IL
The alarm silence function is primarily intended for
use in small installations where the alarm output
directly operates an annunciator such as a sounder.
When the alarm silence time is set to any figure
other than zero, the BA588E Rate Totaliser
(
push
button becomes an alarm accept button.
After an alarm has occurred, operating the
(
button will cause the alarm output to revert to the
non-alarm condition for the configured alarm silence
time. When an alarm is silenced the alarm
annunciator will flash until the silence time expires.
To adjust the alarm silence time select
5iL
using the
&
or
*
push button in the selected alarm sub-
menu and press
(
which will reveal the existing
alarm silence time in seconds with one digit flashing.
The required silence time can be entered using the
&
or
*
push button to adjust the flashing digit and
the
(
button to transfer control to the next digit.
When set as required press
)
to enter the value
and return to the
5iL
prompt in the alarm sub-menu.
10.3.11 Flash display when alarm occurs:
FL5H
In addition to the two alarm annunciators on the
lower left hand side of the Rate Totaliser display
which show the status of both alarms irrespective of
which input is being displayed, this function provides
an even more conspicuous indication that an alarm
condition has occurred.
When enabled and the Rate Totaliser is displaying
the input on which the alarm has occurred, the
fla5h
function alternates the rate or total display
between the numerical value and the alarm
identification. For example if alarm 1 has been
activated by a rate alarm occurring on input A the
rate display will alternate between the numerical rate
value and
AL1
, plus the input identification
in - A
if
5td
has been selected for the lower display
configuration
di5P-2
See 5.11.
Note:
When an alarm occurs on one input the flash
function will only be seen when viewing that
input, not when the Rate Totaliser is showing
the other input or the composite display.
However, the two alarm annunciators, which
indicate the status of each alarm, are
activated irrespective of which input is being
displayed.
To enable the function select
FL5H
from the alarm
sub-menu using the
&
or
*
push button and press
(
to check or change the function. The
&
or
*
push button will toggle the function between
oFF
and
on
, when set as required, press the
)
button to
return to the
FL5H
prompt in the alarm sub-menu.
10.3.12 Access Setpoints:
AC5P
This function activates a separate menu that
provides direct access to the alarm setpoints from
the totalising mode by simultaneously operating the
(
and
*
buttons. An operator can therefore
adjust the alarm setpoints without having access to
the configuration and alarm sub-menus. Protection
against unauthorised or accidental adjustment is
provided by a separate optional security access
code.
Using the
&
or
*
push button select
AC5P
from the
configuration menu and press
(
to reach the
enable sub-function
EnbL
. Pressing
(
will reveal
the existing setting which can be toggled between
on
and
oFF
by pressing the
&
or
*
push button.
When set as required, press the
)
button to return
to the
EnbL
prompt from which a separate security
access code can be entered using the
ACCd
sub-
function which can be selected using the
&
or
*
push button.
To enter a new security access code select
ACCd
from the sub-menu and press
(
which will cause
the Rate Totaliser to display
0000
with one digit
flashing. The flashing digit may be adjusted using
the
&
or
*
push buttons, when set as required
operating the
(
button will transfer control to the
next digit. When all the digits have been adjusted
press
)
to return to the
ACCd
prompt. The revised
security code will be activated when the Rate
Totaliser is returned to the totalising mode. Default
security access code
0000
will disable the security
code allowing direct access to the setpoints in the
totalising mode by pressing the
(
and
*
buttons
simultaneously.